Manual BVS 20 ATEX E 105 X
In the factory the cable and conductor entries are
fitted with CEAG type GHG 960 923 P... cable
glands. The dimensions, the clamping ranges for
cables and wires and the torques are shown in
the tables in Annex A (page 22).
If other cable and conductor entries are in stalled,
the required torques and cable diameters will be
found in the appropriate manual.
Intrinsically safe circuits must enter and leave
the enclosure via separate cable entries that are
specially marked (for example with a light blue
color).
If any cable and conductor entries are not used
or are no longer needed, the tapped holes and
redundant gland bodies must be blanked off with
suitable blind plugs or caps.
4.4
Equipotential bonding and
PE conductor
From the standpoint of intrinsic safety Ex i, a dis-
tinction must be made between the equipotential
bonding conductors and the PE conductors in
the installation. The bonding conductor is regard-
ed as a passive conducting element that fulfills
the required separation conditions with a 500 V
insulation test. The PE conductor, however, is at
a certain potential in the event of a fault, and is
regarded as an active, non-intrinsically safe ele-
ment.
4.5
Shielded cables in intrinsically
safe circuits
If a cable shield is brought into a Zone 1 or
Zone 0 hazardous area during installation, it
must either be treated as an equipotential bond-
ing conductor or must meet the requirements of
a recognized type of explosion protection.
5.
Servicing and Maintenance
The provisions of IEC 60079-17 'Inspection
and maintenance of electrical installations in
hazardous areas' relating to inspection, ser-
vicing and maintenance must be complied
with. In the course of inspections and main-
tenance work, those components on which
the type of explosion protection is dependent
must be inspected particularly carefully.
Edition August 2022
Copyright
本安电路必须通过单独的电缆引入口进出外壳,
这要进行特别标识(例如,用浅蓝色颜色)。
如果不使用任何电缆和导线引入或者不再需要引
入,开的孔和多余的格兰体必须用合适的盲塞或
帽子进行密封。
4.4
等电位连接和PE 导线
从本质安全电路Ex i 的角度,在安装时必须区分
等电位连接导线和PE 导线。等电位连接导线是
一个无源导电元件,要满足500 伏绝缘试验要求
的隔离条件。然而,PE 导线处于发生故障时的
某一电位,是被认为是一个活跃的,非本安电气
元件。
4.5
本安电路的屏蔽电缆
在安装时,如果电缆屏蔽使用在危险场所1 区或
0 区,必须将其视为等电位连接导体或必须符合
公认的防爆类型。
5.
维修和维护
必须遵守IEC 60079-17 规定"在危险区域电气装
置的维护和保养"的保养和维护规定。在检查和
维护过程中,不同防爆类型的这些元件必须特别
仔细地检查。
15