V8043C, D, F & G MOTORIZED ZONE VALVES
INSTALLATION
CAUTION
Normally it is not necessary to remove the
powerhead from the valve body during
installation. The valve must be disassembled
with the water flow arrow pointing away from the
manual opening or lever slot.
Mounting
The valve may be mounted in any position on a vertical
line. On a horizontal line, the valve must be mounted so
that the powerhead is even with or above the center line of
the piping as shown in Fig. 3. Make sure that enough room
is provided above the powerhead to remove the cover for
servicing. See Fig. 1.
Mount the valve directly in the pipe or tube. It must be
installed so that the arrow stamped on the valve body's
side corresponds to the flow direction. For flare-fitting
models, the body is threaded for standard 3/8 in. I.D.
copper, 45 degree SAE flare-fitting nuts. These nuts are
not furnished with the valve and must be obtained
separately. For sweat copper fittings, make sure that good
solder connections are made. DO NOT use silver solder
because of the high melting temperature it requires.
HORIZONTAL
PIPING
VERTICAL
PIPING
Fig. 3. Mounting Positions.
IMPORTANT:
For normally closed models with sweat fittings, set
the opener lever to 'MAN. OPEN' before applying
heat to the fittings. This will protect the plug inside
the valve by removing it from the seat. After instal-
lation, place the manual opener in the 'AUTO' posi-
tion.
Take care not to burn the plastic portion of the
composite adapter plate when soldering.
95C-10002EF—03
NOTE: New Buna-N rubber ball plug is impervious to
boiler or system additives. Petroleum based addi-
tives do not affect this ball plug. Steam applica-
tions require special ball plugs. Consult your local
Resideo representative.
WIRING
All wiring must conform to local electrical codes and
ordinances. Refer to Figs. 4 to 7 for wiring connections.
R
"BLIND"
TERMINAL
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
24V
TRANSFORMER
TO 120V
LINE
1
M10162A
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
YELLOW LEADS TH AND TR ON F MODEL
3
RED LEADS IDENTIFIED AS "END SWITCH" ON F MODEL
4
THERMOSTAT
ENCLOSURE FOR
(TYPICALLY T87)
END SWITCH TERMINALS
TO CIRCULATOR
OR ANOTHER
VALVE
END SWITCH
TH-TR
TH
TR
24V
TRANSFORMER
Fig. 4. V8043F Wiring.
THERMOSTAT
(TYPICALLY T87)
R
2
TO LOW VOLTAGE CIRCULATOR
OR ANOTHER VALVE
3
MOTOR
AUX
SWITCH
Fig. 5. V8043G Wiring.
1
TO 120V
LINE
M16852
M16853