Installation Instructions; Warning Notes; Remove The Battery Fuse; Insert The Battery Fuse - Tunstall USV 60 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5

Installation instructions

5.1

Warning notes

Risk of electric shock!
While the housing of the battery set is open, the mains connection
cable connected to the power supply unit UPS 60 must be dis-
connected from the mains supply.
If this is not oberserved, touching live parts can result in death or
serious injury.
Lead-acid AGM batteries contain hazardous, poisonous substances.
When handling the batteries, and during transport and disposal,
local regulations must be adhered to.
WARNING!
Batteries are subject to the risk of an excessively high short-circuit
cur-rent. To prevent this, do not connect anything between the bat-
tery con-tacts and other conductive parts.
5.2

Remove the battery fuse

The battery set may only be connected to the power supply unit while the internal
battery fuse (7) in the battery set is removed. Proceed as follows to remove the
fuse:
1.
Remove the six fastening screws from the housing cover and remover the co-
ver by pulling it towards you. Do not disconnect the existing earth connection
between housing cover and housing.
-
It will now be possible to access the battery fuse (7) located between the two
batteries.
2.
Remove the battery fuse (7) from the fuse holder and place it in a safe place.
-
The battery fuse is removed. The battery set can now be connected to the
power supply unit. Please refer to the instruction manual for the power supply
unit for information on how to do this.
5.3

Insert the battery fuse

If all connections are made to the power supply unit and the power supply unit is
to be put into operation, the battery fuse (7) must be inserted into the fuse holder
of the battery set:
1.
Insert the battery fuse (7) into the fuse holder located between the two batte-
ries.
2.
Replace the housing cover and screw in the six fastening screws tightly.
The battery fuse is inserted. The battery set is ready for operation. Please re-
fer to the instruction manual for the power supply unit for further information on
how to put the power supply unit into operation.
Battery set for UPS 60 (77 3450 00) – Instruction manual – 00 8802 82, 02/18 (Rev. 6.1)
Remove any watches, bracelets, rings and other metal objects
before starting work on the open battery set.
Only use tools with handles that have standard insulation.
Installation instructions
│10

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ups 60Asi 6077 3450 00

Table des Matières