The battery set for UPS 60 is designed for wall mounting preferably underneath
the power supply. Use the mounting material supplied with it. You should check
the mounting wall beforehand to verify whether it is suitable for fixing the power
supply UPS 60 and the battery set for UPS 60 onto it:
- Weight of the battery set for UPS 60: approx. 25.2 kg
- Dimensions: 244 x 450 x 178 mm
The distance between the power supply unit and the battery set must be large
enough (> 100 mm) to allow easy access to the terminals and fuses on the bot-
tom of the power supply unit.
Insufficient air convection may result in the power supply unit being destroyed.
For this reason, you must observe the following points:
The ventilation openings on the device must be located at the top and bot-
tom.
You must ensure that air can circulate sufficiently above and below the de-
vice. Therefore, there must be a distance of at least 50 mm between the de-
vice and other devices or walls.
Do not cover the ventilation outlets under any circumstances.
Fig. 1: Dimensional drawing
Battery set for UPS 60 (77 3450 00) – Instruction manual – 00 8802 82, 02/18 (Rev. 6.1)