To Reposition The Air Thermistor On The Outdoor Unit - Daikin Altherma 3 H MT EPRA08EAV3 Manuel D'installation

Masquer les pouces Voir aussi pour Altherma 3 H MT EPRA08EAV3:
Table des Matières

Publicité

1
2
3
3 (Optional) Drain tube heater cable:
▪ Make sure the heating element of the drain tube heater is
completely inside the drain tube.
▪ Route the cable through the frame.
▪ Connect the wires to the terminal block and the earth screw.
▪ Fix the cable with cable ties.
Wires: (2+GND)×0.75 mm². Wiring must be double insulated.
Maximum power allowed for drain tube heater = 115 W (0.5 A)
EPRA08~12EAV3+W1
Daikin Altherma 3 H MT
4P634882-1B – 2021.09
1 2 3
6.5
This procedure is only necessary in areas with low ambient
temperatures.
Required accessory (delivered with the unit):
2
4
6
6 Electrical installation
1 2
To reposition the air thermistor on
the outdoor unit
Thermistor fixture.
1
3
5
7
Click
Installation manual
15