Cable types and minimum thicknesses
CABLE LENGTH (m)
230 V AC Power supply
-|24v-- 24 V AC - DC Flashing light|-
TX Photocells
RX photocells
Command and control devices
Antenna
*no. = see product mounting instructions - Warning: the cable section is merely indicative as it depends on the motor power and cable length.
For installation in an outdoor environment, use cables with properties equivalent to at least those of type H05RN-F (with designation 60245 IEC 57).
For installation in an indoor environment, use cables with properties equivalent to at least those of type H05VV-F (designation to 60227 IEC 53).
If cable lengths differ from those specified in the table, establish the cable sections depending on the actual power draw of the connected devices and
according to the provisions of regulation CEI EN 60204-1.
For multiple, sequential loads along the same line, the dimensions on the table need to be recalculated according to the actual power draw and
distances. For connecting products that are not contemplated in this manual, see the literature accompanying said products
For combined connection and CRP, use a UTP CAT5-type cable. Maximum length 1000 metres.
Wind resistance
Type
Resistance class
Wind pressure [Pa]
Maximum wind speed [km/h]
< 10
3G x 1.5 mm²
2 x 1 mm²
2 x 0.5 mm²
4 x 0.5 mm²
*n° x 0.5 mm²
Boom 3.05 m
4
1000
132
from 10 to 20
3G x 1.5 mm²
2 x 1 mm²
2 x 0.5 mm²
4 x 0.5 mm²
*n° x 0.5 mm²
RG58 max 10 m
from 20 to 30
3G x 2.5 mm²
2 x 1 mm²
2 x 0.5 mm²
4 x 0.5 mm²
*n° x 0.5 mm²
Boom 4.05 m
3
800
118