3.3.4 Enabling / Disabling Temperature Curve
1. Follow the procedure above (3.3) and press Enter
The following parameters can only be accessed if the zone has been
configured with a temperature curve.
TEMP. CURVE
STATUS: ENABLED
ENABLE. . . . . (1)
DISABLE. . . . . (2)
2. Type 1 to enable or 2 to disable the temperature zone for this zone.
START DAY: _ _ _
3. If you have chosen to enable the curve, you can adjust the start day for the curve.
Enter the start day and press Enter
3.3.5 Adjusting the Recognition Time
Definition: The recognition time is the time an alarm input must be active before it
constitutes a valid alarm condition. It is used to configure all alarm inputs except
burglar inputs.
1. Follow the procedure above (3.3) and press Enter
RANGE FROM
(0 .. 59 HR, 0 .. 59 MIN, 0 .. 59 SEC)
RECOGNITION TIME
_ _ :_ _ : _ _
2. To enter the recognition time, enter the hours; press Enter. Enter the minutes;
press Enter. Enter the seconds; press Enter.
26
KP-400.rev.06
ENTER
.
ENTER
at TEMP. CURVE.
at REC. TIME.
ENTER