SABROE ChillPAC Mode D'emploi page 66

Table des Matières

Publicité

1.
Open the tightening screw (pos. 1) on the meta glass connector and the fixing screw
(pos. 2), see Fig. 28.
2.
Fit it carefully on the process connector. The loose screw (pos. 1) gives way for the
trapped air so the signal converter can be installed. It should be pressed down carefully,
yet with some force, to fit over the o-ring.
3.
Now tighten both screws carefully according to the AKS instructions.
4.
When power is connected, and the screen is starting up, do a quick set-up according to
the instructions in Fig. 29.
AKS 4100
Enter menu system
Unit change at
Enter QUICK SETUP
distance/level
readout:
m, cm, mm, in, ft
• Connect the device to the power supply
Connect the device to the power supply
(see the section "Electrical installation/
connection").
• Press
3 times.
AKS 4100
QUICK SETUP ?
YES
NO
• Press
AKS 4100
D22
• Press
or
to select between SINGLE,
COAXIAL D14 and COAXIAL D22. Choose
D22 and press
AKS 4100
CO2?
YES
• Press
AKS 4100
PROBE LENGTH
00280 mm
Fig. 29: Quick set-up of AKS 4100 280 mm
*
Note:
The signal converter can be programmed with or without mechanical process
connector assembled.
To con gure the signal converter, a HMI display is always needed.
Change between:
Distance*
Level**
Output (%)***
Output (mA)****
• Press
to change the PROBE LENGTH.
Press
to change the position of the
cursor.
Press
to decrease the value or
increase the value.
Press
AKS 4100
SCALE 4 mA
• Press
to change of SCALE 4 mA.
Press
to change the cursor position.
Press
to decrease the value or
increase the value.
Press
AKS 4100
SCALE 20 mA
NO
• Press
to change of SCALE 20 mA.
Press
to change the cursor position.
Press
to decrease the value or
increase the value.
Press
to
• Wait for QUICK SETUP to complete.
Count down from 8 sec.
210 mm
• Press
to
• Press
STORE NO or STORE YES.
00060 mm
Press
Default screen appears:
DISTANCE
to
QUICK SETUP completed
Mode d'emploi – ChillPAC et LP ChillPAC Mk 3
66/79
Annexes
AKS 4100
QUICK SETUP
COMPLETED IN 8
AKS 4100
AKS 4100
1.0.0
QUICK START
QUICK SETUP ?
YES
NO
AKS 4100
1.0.0
STORE NO
or
to select between
AKS 4100
XXX mm
010823 fr 09/2022