Définition Du Code De Numérotation - Bosch Climate 5000 VRF Guide Technique

Masquer les pouces Voir aussi pour Climate 5000 VRF:
Table des Matières

Publicité

Régulateurs VRF
Définition du code de numérotation
1) Définition SW1
S W1
● 1 means the factory test mode
ON
● 0 automatic search address mode
(factory default)
1234
S W1
● 1 means select DC fan(reserved)
ON
● 0 means select AC fan
1234
S W1
● 00 means DC fan static pressure
ON
selection 0 set (reserved)
1234
S W1
● 00 means DC fan static pressure
ON
selection 0 set (reserved)
1234
S W1
● 01 means DC fan static pressure
ON
selection 1 set (reserved)
1234
S W1
● 10 means DC fan static pressure
ON
selection 2 set (reserved)
1234
S W1
● 11 means DC fan static pressure
ON
selection 3 set (reserved)
1234
2) Définition SW2
y
p
SW2
● 00 means temperature of
ON
shut down against cool air
is 15°C
1234
SW2
● 01 means temperature of
ON
shut down against cool air
is 20°C
1234
SW2
● 10 means temperature of
ON
shut down against cool air
is 24°C
1234
● 11 means temperature of
SW2
ON
shut down against cool air
is 26°C
1234
S W2
ON
● 00 means the time of TERMAL
stop the fan is 4 minutes
1234
S W2
● 01 means the time of TERMAL
ON
stop the fan is 8 minutes
1234
S W2
● 10 means the time of TERMAL
ON
stop the fan is 12 minutes
1234
S W2
● 11 means the time of TERMAL
ON
stop the fan is 16 minutes
1234