Power Supply Components; Leds Indication - RISCO Group SMPS Guide D'installation

Alimentation en mode commuté (3a)
Masquer les pouces Voir aussi pour SMPS:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Power Supply Components

The LEDs, Dipswitches, jumpers, and terminals functions are described
herein.

LEDs Indication

LED
PS (Power Supply
Communication)
UO
(Utility Output
Communication)
OC
(Over Current)
NOTE:
To calculate sounder's current consumption, the Sounder must be operated at
least once (recommended to be performed upon installation completion).
10
Description
Indicates communication status between the Power
Supply and the Main Panel.
On: Normal communication with the Main Panel.
Off: No input power
Flashing: Bus communication failure, system in
installation mode or PS dipswitch 4 is OFF.
Indicates communication status between the SMPS UO
module and the Main Panel.
On: Normal communication with the Main Panel.
Off: No voltage power
Flashing: Bus communication failure, system in
installation mode or UO dipswitch 4 is OFF.
Indicates an actual/potential (calculated) overload.
On: Total current consumption from the AUX and
BELL/LS outputs exceeded 3A (power consumption
from both outputs will be disconnected).
Off: Normal current draw
Flashing: The SMSP detected a potential current
overload when calculating the total value of real current
consumption from the AUX output and expected current
consumption from the BELL/LS output.
SMPS - Installation Guide