1. Product description

The TRI CMV pressurization system was designed
to pressurize clean water.
Examples:
• building blocks
• hotels
• schools
The TRI CMV consists of three identical pumps
connected in parallel and mounted on a common
base, collector compression, isolating valves,
check valves, pressure gauge, pressure switches
and a control cabinet.
See Pic. 1.
1
2
3
Pic.1
1 - Control panel
2 - Pumps (CMV)
3 - Check Valves
4 - Pressure gauge
5 - Pressure switches
6 - Discharge Manifold
7 - Inlet manifold (not included in the standard
version)
8 - Base
You must be always install a
membrane tank in the discharge side
of the pressurization system.

2. Operating conditions

Max. flow:
Max. Operat. Pressure:
Liquid temperature:
Ambient temperature:
Power range:
Boot method:
Power supply:
3. Installation
- Before the installation confirm that the system
corresponds to the request and if any part is
damaged.
- The system should be in place that allow a good
cooling system, as well as the cooling fans should
be kept clean.
- The central TRI is not suitable for outdoor
installation, and should be protected from
frost, direct sunlight and rain.
4
5
- The system should be placed on a flat solid
surface and must be fixed to the ground.
6
7
4. Tubing
8
- The pipes connected to the pressurization
system must have the appropriate size.
- Connect the pipes to the collectors of the
pressurization system.
- Can be used either end.
- For optimum operation and reduce noise and
vibration, may need to install vibration dampers.
- If the pressurization system is installed in a block
of apartments or the first consumer line is near the
pressurization system, we recommend the
installation of compensation joints in suction and
discharge pipes to prevent the vibration is
transmitted through pipes.
NOTE: The deposit of the membrane, gaskets
and shims to compensate the machine are not
provided with the system.
1
3
up to 66 m /h
10 bar
+5 a +40ºC
+5 a +55ºC
até 4 Kw
Direct
1x220V
10% 50Hz
+/-
3x400V
10% 50Hz
+/-