I N S TA L L AT I O N
S T E P 3
Output Wiring
1. Strip away a minimum of 1 in (25 mm) of the outer cable jacket from the 4-conductor cable
(QSH-CBL(P)-M or equivalent.). The shield and drain may be left floating.
2. Separate each conductor.
3. Strip ¼ in (6 mm) of insulation from each conductor .
4. Install the connector by arranging the four conductors by color and number according to the
diagram below. Depress the plunger on the plug, insert the wire, and then release the plunger.
NOTE: Pliers can be used to depress plungers if needed.
Press here, insert wire, release.
Red | V+
White | DATA-
Purple | DATA+
Black | COM
8 | X96 INSTALLATION GUIDE
COM
Q S H - C B L (P) - M - 5 00 C A B L E
16 AWG (1.5 mm²)
16 AWG (1.5 mm²)
22 AWG (0.50 mm²)
22 AWG (0.50 mm²)
22 AWG (0.50 mm²) Drain
0.35 in (9 mm)
© 2021 Lutron Electronics Co., Inc.
P/N 3662663 Rev A