• Check the condition of the fan on a monthly basis to avoid corrosion problems,
especially in the possible contact areas between moving and xed parts.
• Frequent checks are required on the bearings and ensuring they have enough
grease. It is good practice to rotate the propeller or impeller to avoid damage
to the bearings due to the weight of these components.
• It is advisable to seal the suction and discharge mouth of the fan in order to
prevent the entry of foreign bodies.
• Avoid storage for long periods of time. We do not recommend storing the equi-
pment for more than one year, and we advise consulting the manufacturer
before starting up for periods longer than this.
SAFETY INSTRUCTIONS
This section contains instructions to prevent damage to persons and property.
These instructions are not exhaustive and you should contact the manufacturer
if you have any questions.

USE ACCORDING TO INTENDED PURPOSE

The company installing the fan must ensure that it is only used for its intended purpose and
that it is in good condition and suitable for operation.
Only fans that are marked with the
potentially explosive atmosphere.
The intended use and limits of application are indicated on the product's name plate or in the
accompanying instructions.

AREA OF APPLICATION

This fan complies with the construction requirements for categories 2 and 3 of equipment
class II G (explosion group IIA, IIB and hydrogen) and categories 2 and 3 of group II D of Direc-
tive 2014/34/EU and is therefore not suitable for group I applications, or category 1 classi ca-
tions of group II G or II D. The fan group is indicated on the fan's name plate.
This fan is intended for use in potentially explosive atmospheres containing gas, vapour, mist
and/or dust. Such atmospheres may exist inside transported uid, outside, or inside and
outside the fan. Please keep in mind the maximum atmospheric conditions speci ed in EN
14986.
EXPLOSION PROTECTION CATEGORY
This fan can only be used in the areas suitable for its explosion protection category. This ca-
tegory is indicated on the name plate.
• Gas explosion group
Category 2G and 3G. Fans intended for use in the extraction of potentially explosive atmos-
pheres in explosive groups IIA and IIB (EN60079-20) belong to this category. Under certain
conditions these fans can also be used for the extraction of gases and vapours containing
20
symbol may be used in areas classi ed as having a