Télécharger Imprimer la page

Siemens MICROMASTER 420 Mode D'emploi page 21

Masquer les pouces Voir aussi pour MICROMASTER 420:

Publicité

Start Quick Commissioning
P0010
P0010 must always be set back to '0' before
1 = Quick
operating the motor. However if P3900 = 1 is set
Commissioning
after commissioning this is done automatically
Operation for Europe / N. America
P0100
For setting 0 and 1 use DIP Switch 2.
0 = kW / 50 Hz
For setting 2 use P0100
1 = hp / 60 Hz
2 = kW / 60 Hz
Rated Motor Voltage
P0304
Nominal motor voltage (V) from rating plate
10 V - 2000 V
Rated Motor Current
P0305
Nominal motor current (A) from rating plate
0 ... 2 * I nom
Rated Motor Power
P0307
Nominal motor power (kW) from rating plate. If
0 kW - 2000 kW
P0100 = 1, values will be in hp
Rated Motor Frequency
P0310
Nominal motor frequency (Hz) from rating plate
12 Hz - 650 Hz
MICROMASTER 420/430/440, Getting Started Guide 10/08
English
Deutsch
Start Schnellinbetriebnahme
P0010 muss vor der Betrieb des Motors auf '0'
zurückgesetzt werden. Wird nach der
Inbetriebnahme P3900 = 1 eingestellt, dann
erfolgt dies automatisch.
Betrieb für Europa / Nordamerika
Die Einstellungen 0 und 1 sind über
DIP-Schalter 2 herzustellen.
Einstellung 2 über P0100
Motornennspannung
Motornennspannung (V) vom Typenschild des
Motors
Motornennstrom
I nom = Motornennstrom (A) vom
Typenschild
Motornennleistung
Motornennleistung (kW) vom Typenschild. Bei
P0100 = 1, sind die Werte in hp
Motornennfrequenz
Motornennfrequenz (Hz) vom Typenschild
21

Publicité

loading

Ce manuel est également adapté pour:

Micromaster 430Micromaster 440