This device must be installed by a
suitably qualified electrician according to
the installation's standards.
Product description and operation principles
Occupancy sensors TCC510S are presence detectors
designed to detect low amplitude movements
(movements from body or arms).
Detection is by means of the pyroelectric IR sensor
located under detection lens.
The occupancy sensor measures the
brightness in the room on a continuous basis and
compares it to the level preset on the potentiometer
(or by means of the remote control EE807) by ETS
parameter.
These products are part of the tebis installation sys-
tem.
Configuration
• E-mode TX100 V.2.6.0 or > : detailed
description in User's Instructions supplied with the
configurer.
• S-mode ETS : Application software STCC510S.
Database and description
available from manufacturer.
Physical addressing
Set potentiometer 2 to "Adr." position, the red LED
switches on. To exit this state, move the potentiome-
ter to another value.
Features
• One lighting channel on the KNX bus.
• Control of presence/ absence mode.
• Time and Lux level adjustment via ETS or remote
control EE807.
Settings
The Lux level and time out period can be set with the
potentiometers, by using the installer IR remote
control (EE807) or via ETS.
Test Mode
This mode makes it possible to validate the
detection area. To select this mode, set the
potentiometer 1 to the position "auto test".
The green or red LED behind the lens is on for
2 seconds after detection.
Action
Settings
Use Auto settings
Auto Settings
(factory) or
Put the Lux potentiometer on "auto test".
set by the remote
The settings are predefined :
control or via ETS to
Lux = 400,
switch the light
time = 20min,
automatically for a
: test mode for 2min.
defined time.
Remote control settings EE807
(manual settings inhibited).
Automatically switch
Installer settings
on the light for a
defined time.
Test and validate the
Test mode
detection zone.
Move the potentiometer
On this position, the remote control EE807
can be used.
KNX addressing
Move the potentiometer
remote control EE807 (long push > 5s. on the
SET key till the remote control's LED blinks).
Hager Controls S.A.S., 33 rue Saint-Nicolas, B.P. 10140, 67703 SAVERNE CEDEX, France - www.hager.com
4
The red LED indicates that the light level measured is lower
than current setting.
If the green LED is on, the light level measured is higher
than current setting.
There is a time out during 2 minutes which is reactivated
after each detection.
The output (remote KNX load) is switched during 2s. after
each detection.
It is also possible to use the remote control EE807 to set
the detector in test mode if the potentiometer is set on
"auto test".
Functional modes
The detector has 2 different modes.
- Presence detection (automatic).
- Absence detection (semi-automatic)
The power up and cell operation can be set for each
mode.
A KNX pushbutton linked to the product makes it possible
to reverse the lighting output state.
This state is maintained for the time period set by the
potentiometer 2 or the remote control EE807.
Automatic mode (presence detection)
In this mode the light is controlled by motion in the detec-
tion area and ambient light levels.
If presence is detected whilst the light levels are below the
required Lux level, the sensor is activated and keeps the
light on whilst there is still occupancy and for the time out
period afterwards.
Once the sensor has deactivated the lights, it will require a
new occupancy whilst the ambient light levels are below
the required Lux levels to activate the lights again.
This mode can be changed via the IR remote control
EE807 (default mode is presence detection : automatic).
Lighting time delay is restarted after each detection.
Semi automatic mode (absence detection)
The sensor needs to be activated by a KNX
pushbutton or a user remote control input.
Once the sensor is activated, it will hold the lights on whilst
there is still occupancy and for the time out period after-
wards.
Once the sensor has deactivated the lights, it will require
another input from the wallswitch or the remote control to
switch the lights on.
Power Up
A parameter of the detector allows the choice of state for
the lighting after power up (mains return). This parameter is
modified using the installer remote control EE807.
During warm up phase, the green LED blinks.
In the Power up ON state the lighting will automatically be
Potentiometer
auto
test
on
auto
test
on
1 min
1 h
Adr
auto
test
to "auto test".
1
1
on
2
to "Adr." or use
1 min
1 h
Adr
energised when mains power is initially supplied or
returned to the sensor.
In the Power up OFF state the lighting will not
be energised and the sensor will not operate during
warm up period.
POWER UP state :
• ON : The light is immediately switched ON for 30s.
after power up.
In case of detection, the light (in automatic mode)
remains on during the time delay; otherwise the
light is switched off.
• OFF : The detector switches to the selected mode
after warm up.
Active/passive cell
Active cell
The photocell will inhibit the output from the sensor if
the ambient light level is sufficient.
If the sensor detects occupancy whilst the ambient
light level is below the required Lux level, the lights
will be activated. However if the ambient light level
increases to a value where it is above the required
Lux level during a certain time, the sensor will detect
it and switch off the light.
Passive cell
The photocell will inhibit the output from the sensor if
at the time of detection the ambient light level is suffi-
cient. In case of detection, if the ambient light level
increases, the photocell will not turn off the light.
Association of several detectors
It can can be associated with one or several detectors in
order to extend its zone of coverage.
Factory settings
Luminosity threshold
Lighting time
Mode
Power Up
Active cell (Luminosity Cell)
Technical features
Electrical characteristics
Supply voltage :
Busline consumption :
Functional characteristics
Lighting output operating time :
Brightness level :
Recommended installation height :
Detection range :
(installed product height :
Hole size required :
Environment
1
lux
Operating temperature :
Storage temperature :
2
Insulation class :
IK 04
Protection degree :
Fire resistance :
Max installation height :
Rated impulse voltage :
Pollution degree :
Configuration mode:
controller
1
lux
Transmission mode :
2
20 min
This marking shown on the product or its literature indicates
that it hould not be disposed with other household wasted at
the end of its working life. To prevent possible harm to the
environment or human health from uncontrolled waste dispo-
auto
sal, please separate this from other types of wastes and recy-
test
1
cle it responsibly to promote the sustainable reuse of material
lux
lux
resources.
Household users should contact either the retailer where they
2
2
purchased this product, or their local government office, for
details of where and how they can take this item for environ-
on
mentally safe recycling.
Business users should contact their supplier and check the
terms and conditions of the purchase contract. This product
should not be mixed with other commercial wastes of disposal.
20 min
400 lux
20 min.
Presence
OFF
ON
KNX bus 30 V s TBTS
5 ¬1000 Lux
2,5 m ¬3,5m
-10 °C ¬ +45 °C
-20 °C ¬ +60 °C
S mode, Easy link
Correct Disposal of This product (Waste Electrical &
Electronic Equipment).
(Applicable in the European Union and other
European countries with separate collection sys-
tems).
å
Usable in all Europe
and in Switzerland
hager 05/17 6LE002862A
10mA
1min. ¬ 1 h
Ø 7m
2.5m)
60mm
III
IP41
650°C
2000m
800V
2
TP1

Publicité

loading