High Altitude Installation - Enviro 6G50 76N Serie Manuel

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

exceed the marked hydrostatic working pressure of the water heater
(150 psi = 1,035 kPa) and a discharge capacity not less than the
water heater Btu/hr or kW input rate as shown on the water heater's
model rating plate.
Note: In addition to the factory installed Temperature-Pressure
Relief Valve on the water heater, each remote storage tank that
may be installed and piped to a water heating appliance must also
have its own properly sized, rated and approved Temperature-
Pressure Relief Valve installed. Call the toll free technical support
phone number listed on the back cover of this manual for technical
assistance in sizing a Temperature-Pressure Relief Valve for remote
storage tanks.
For safe operation of the water heater, the Temperature-Pressure
Relief Valve must not be removed from its designated opening
nor plugged. The Temperature-Pressure Relief Valve must be
installed directly into the fitting of the water heater designed for the
relief valve. Install discharge piping so that any discharge will exit
the pipe within 6 inches (15.2 cm) above an adequate floor drain,
or external to the building. In cold climates it is recommended
that it be terminated at an adequate drain inside the building. Be
certain that no contact is made with any live electrical part. The
discharge opening must not be blocked or reduced in size under
any circumstances. Excessive length, over 30 feet (9.14 m), or use
of more than four elbows can cause restriction and reduce the
discharge capacity of the valve.
No valve or other obstruction is to be placed between the
Temperature-Pressure Relief Valve and the tank. Do not connect
discharge piping directly to the drain unless a 6" (15.2 cm) air gap
is provided. To prevent bodily injury, hazard to life, or property
damage, the relief valve must be allowed to discharge water in
adequate quantities should circumstances demand. If the discharge
pipe is not connected to a drain or other suitable means, the water
flow may cause property damage.
CAUTION
Water Damage Hazard
Temperature-Pressure Relief Valve discharge
pipe must terminate at adequate drain.
t&p valve discharge pipe requirements:
• Should not be smaller in size than the outlet pipe size of the valve, or
have any reducing couplings or other restrictions.
• Should not be plugged or blocked.
• Should not be exposed to freezing temperatures.
• Should be of material listed for hot water distribution.
• Should be installed so as to allow complete drainage of both the
Temperature-Pressure Relief Valve and the discharge pipe.
• Must terminate a maximum of six inches above a floor drain or external
to the building. In cold climates, it is recommended that the discharge
pipe be terminated at an adequate drain inside the building.
• Should not have any valve or other obstruction between the relief
valve and the drain.
All manuals and user guides at all-guides.com
16
DANGER
The Temperature-Pressure Relief Valve must be manually
operated at least twice a year. Caution should be taken to ensure
that (1) no one is in front of or around the outlet of the Temperature-
Pressure Relief Valve discharge line, and (2) the water manually
discharged will not cause any bodily injury or property damage
because the water may be extremely hot. If after manually
operating the valve, it fails to completely reset and continues
to release water, immediately close the cold water inlet to the
water heater, follow the draining instructions in this manual, and
replace the Temperature-Pressure Relief Valve with a properly
rated/sized new one.
note: The purpose of a Temperature-Pressure Relief Valve is to
prevent excessive temperatures and pressures in the storage tank.
The T&P valve is not intended for the constant relief of thermal
expansion. A properly sized thermal expansion tank must be
installed on all closed systems to control thermal expansion, see
Closed Water Systems and Thermal Expansion on page 14-15.
If you do not understand these instructions or have any questions
regarding the Temperature-Pressure Relief Valve call the toll
free number listed on the back cover of this manual for technical
assistance.

hIGh altItude InstallatIon

This heater is approved for operation up to 5,300 feet (1,615 m)
without alteration. High altitude models are available from the
factory for elevations between 5,300 feet (1,615 m) and 10,100
feet (3,079 m). For elevations above 10,100 feet (3,079 m) the
input rating should be reduced at the rate of 4 percent for each
1,000 feet (305 m) above sea level which requires replacement
of the burner orifice. Contact your local gas supplier for further
information.
Burn hazard.
Hot water discharge.
Keep clear of Temperature-
Pressure Relief Valve
discharge outlet.

Publicité

Chapitres

Table des Matières

Dépannage

loading

Table des Matières