Numatics ControlNet G2-2 Serie Manuel page 8

Masquer les pouces Voir aussi pour ControlNet G2-2 Serie:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

9) Auxiliary Power Connector Pin-Out
Pin No.
1
(Valves and Outputs)
2
3
4
(Node and Inputs)
!
G2-2 Series ControlNet Quick Start Manual
Function
+24VDC
Voltage Used to Power Outputs
(Valve Coils and Discrete Outputs)
Earth Ground
Protective Earth (Case Ground)
0VDC Common
0VDC Common, for Valves, I/O, and Node Power
+24VDC
Voltage Used to Power Discrete Inputs and Node Electronics
Maximum current capacity on the 0VDC common pin of the auxiliary
power connector is 8 Amps. The combined draw of the +24VDC Valves and
Outputs and +24VDC Node and Inputs pins cannot exceed 8 Amps, at any
given moment in time.
The auxiliary power +24VDC Node and Inputs pin supplies power to the
node electronics. This pin must be powered at all times for communication
node to be functional.
3835052 TDG22CNQS4-0
Subject to change without notice
www.numatics.com/fieldbus
Description
4
1
3
2
1/07
Page 8

Publicité

Table des Matières
loading

Table des Matières