Getting Started
This is a brief document designed to quickly get you started setting up your valve manifold with an integrated
Numatics' G2-2 Series A-B 1771 Remote I/O communication node. Please note that this document is not
intended to replace the G2-2 Series A-B 1771 Remote I/O Technical Manual, which includes more detailed
technical information. The full technical manual can be found on the Numatics website at
www.numatics.com
1) Initial Unpacking and Inspection
1) Examine exterior of package for signs of damage. Report any damage to shipping carrier.
2) Remove wrapped manifold assembly from box.
a) Remove manifold assembly from anti-static packaging
b) Retain documentation for installation and configuration
3) Examine manifold assembly for any shipping damage such as:
a) Bent pins or connectors
b) Report any damage to shipping carrier immediately
4) Examine manifold assembly for proper ordered configuration. (Valves, I/O, Protocol, etc.)
2) G2-2 Introduction
Below is an example of a 2012 series valve manifold. This fieldbus manifold series is capable of addressing a
total of 128 I/O (up to 1 full rack size). The manifold can be viewed as having two sections to it, the
Side
Discrete I/O Side
and the
I/O Side
supports a maximum of 6 modules totaling 110 I/O. The communication module has two
connectors: a 5-pin communication connector and a 4-pin power connector. Pin-outs for these, along with
I/O connectors, and are labeled on the side of the respective modules.
Discrete I/O
Connectors
I/O Point
LED Status
Indicator(s)
Dual 25 Pin Sub-D
w/Aux Power
Output Module
Connector Module
All manuals and user guides at all-guides.com
G2-2 Series A-B 1771 Remote I/O
or may be ordered by calling 248-887-4111.
Valve Side
. The
Discrete I/O Side
(Maximum of 6 Modules)
19 Pin Round
8 Connector I/O Module
Terminal Strip Module
3835050 TDG22ABQS3-0
Subject to change without notice
www.numatics.com/fieldbus
Quick Start Manual
supports a maximum of 32 solenoid coils and the
Valve Side
(Maximum of 32 Solenoids)
Module/
Chassis Ground
Network
Connection
Status LED's
COMM. STATUS
A-B
1771 RIO
FUSE 1
+24V VLV/OUT
FUSE 2
+24V NODE/IN
Valve Side
Sub-D Output
Module
Communications
Module (Node)
Manual Configuration
Module (MCM)
1/07
Valve
Discrete
Valve
End Plates
Valve
Manual
Override
Solenoid LED
Status Indicator
Page 1

Publicité

loading

Sommaire des Matières pour Numatics G2-2 Serie

  • Page 1 This is a brief document designed to quickly get you started setting up your valve manifold with an integrated Numatics’ G2-2 Series A-B 1771 Remote I/O communication node. Please note that this document is not intended to replace the G2-2 Series A-B 1771 Remote I/O Technical Manual, which includes more detailed technical information.
  • Page 2 The MCM consists of two DIP switch sets (SW1 and SW2) and two rotary switches (SW3 and SW4). MCM Module Part Numbers Description Part Number Complete Module 239-1384 Replacement Board 256-684 3835050 TDG22ABQS3-0 1/07 Subject to change without notice www.numatics.com/fieldbus Page 2...
  • Page 3 0 Coils Any Other Setting 32 Coils Rotary Switch Settings (SW3 and SW4) Rack Address (Decimal): Switch Description Sets the Ones Digits Sets the Tens Digits Factory Default Settings 3835050 TDG22ABQS3-0 1/07 Subject to change without notice www.numatics.com/fieldbus Page 3...
  • Page 4 Air should be disconnected to the manifold when attempting to run the Self-Test Mode to prevent unwanted motion. Communication lines should be disconnected before attempting to run the Self-Test Mode. 3835050 TDG22ABQS3-0 1/07 Subject to change without notice www.numatics.com/fieldbus Page 4...
  • Page 5 When the 12 End When the 14 End Reserved Inputs = 4 Solenoid is Solenoid is Total Inputs = 16 energized, the 2 port energized, the 4 port is pressurized. is pressurized. 3835050 TDG22ABQS3-0 1/07 Subject to change without notice www.numatics.com/fieldbus Page 5...
  • Page 6 Discrete Discrete Discrete Discrete Discrete Input No. 7 Input No. 6 Input No. 5 Input No. 4 Input No. 3 Input No. 2 Input No. 1 Input No. 0 3835050 TDG22ABQS3-0 1/07 Subject to change without notice www.numatics.com/fieldbus Page 6...
  • Page 7 Short Circuit, Over Temp/Over Current 7) Ground Wiring All Numatics Inc. communication nodes should be grounded during the installation process. These grounding guidelines can be found in National Electrical code IEC 60204-1 or EN 60204-1. There also is a, “ATTENTION: CONNECT TO EARTH GROUND FOR PROPER GROUNDING OF UNIT”, label attached to the chassis ground connection point on the G2-2 series communication node housing.
  • Page 8 The auxiliary power +24VDC Node and Inputs pin supplies power to the node electronics. This pin must be powered at all times for communication node to be functional. 3835050 TDG22ABQS3-0 1/07 Subject to change without notice www.numatics.com/fieldbus Page 8...
  • Page 9 No DC Power present at +24V pin on Aux. Power NODE / IN +24V NODE/IN Green connector. +24V DC Power applied to pin on Aux. Power connector. NODE / IN 3835050 TDG22ABQS3-0 1/07 Subject to change without notice www.numatics.com/fieldbus Page 9...
  • Page 10 Self-Configuring based on the I/O modules installed. 11) Technical Support For technical support, contact your local Numatics distributor. If further information is required, please call Numatics Inc. at (248) 887-4111 and ask for Technical Support. Issues relating to network set-up, PLC programming, sequencing, software related functions, etc…...
  • Page 11 A-B 1771 série G2-2 intégré. Veuillez noter que ce document n'est pas destiné à remplacer le Manuel technique A-B 1771 Remote E/S Série G2-2 qui contient des informations techniques plus détaillées. Veuillez télécharger le manuel technique complet sur le site web Numatics www.numatics.com ou le commander par téléphone au 248-887-4111.
  • Page 12 DIP switchs (SW1 et SW2) et de deux roues codeuses (SW3 et SW4). Codes des composants du module MCM Description Code Module complet 239-1384 Carte de rechange 256-684 3835050 TDG22ABQS3-0 1/07 Sous réserve de modification sans avis préalable www.numatics.com/fieldbus Page 2...
  • Page 13 Réglages des roues codeuses (SW3 et SW4) Adresse du rack (décimal) : Switch Description Mise au point des chiffres des unités Mise au point des chiffres des dizaines Réglage usine 3835050 TDG22ABQS3-0 1/07 Sous réserve de modification sans avis préalable www.numatics.com/fieldbus Page 3...
  • Page 14 Avant de lancer le mode auto-test, coupez l'alimentation en air de l'îlot pour prévenir les mouvements accidentels. Débranchez les câbles de communication avant de lancer le mode auto-test. 3835050 TDG22ABQS3-0 1/07 Sous réserve de modification sans avis préalable www.numatics.com/fieldbus Page 4...
  • Page 15 Solenoid is energized, the 2 port energized, the 4 port Entrées allouées et is pressurized. is pressurized. Mot 0; Bits 4-7 réservées = 4 Nb. total d'entrées = 3835050 TDG22ABQS3-0 1/07 Sous réserve de modification sans avis préalable www.numatics.com/fieldbus Page 5...
  • Page 16 Entrée discrète Entrée discrète 0 réservé réservé réservé réservé Entrée Entrée discrète Entrée discrète Entrée discrète Entrée discrète Entrée discrète Entrée discrète Entrée discrète 0 discrète 7 3835050 TDG22ABQS3-0 1/07 Sous réserve de modification sans avis préalable www.numatics.com/fieldbus Page 6...
  • Page 17 7) Mise à la terre Tous les nœuds de communication de Numatics Inc. doivent être mis à la terre pendant la procédure d'installation. Les exigences relatives à la mise à la terre sont fournies dans les normes CEI 60204-1 ou EN 60204-1.
  • Page 18 La broche d'alimentation auxiliaire +24VCC du nœud et des entrées alimente l'électronique du nœud. Cette broche doit être alimentée en tension à tout moment pour permettre au nœud de communication de rester opérationnel. 3835050 TDG22ABQS3-0 1/07 Sous réserve de modification sans avis préalable www.numatics.com/fieldbus Page 8...
  • Page 19 Pas de courant CC présent sur la broche VLV / OUT connecteur d'alimentation auxiliaire. +24V NODE/IN Vert Courant CC appliqué à la broche +24V du connecteur NODE / IN d'alimentation auxiliaire. 3835050 TDG22ABQS3-0 1/07 Sous réserve de modification sans avis préalable www.numatics.com/fieldbus Page 9...
  • Page 20 … Les informations sur les fichiers des périphériques, les manuels techniques, les distributeurs locaux, ainsi que d'autres informations sur les produits et le support Numatics Inc. se trouvent sur le site web Numatics Inc. sous www.numatics.com...