The LED floodlight must be protected on the sub-distribution board by a
10/16A fuse. An earth leakage circuit breaker must be installed before
this (FI protective switch).
The LED floodlight must be disconnected from the power supply during
installation. It is not sufficient to just turn off at the light switch!
Turn the power off by removing the corresponding circuit fuse or switch
off at the circuit breaker. Secure it against an unauthorised re-start, e.g.
with a danger sign. In addition, switch off the associated earth-leakage
circuit breaker.
Check that the mains connection is current free with a suitable tester.
The earth protection cable must be connected when installing the LED
floodlight.
Do not install the LED floodlight, if the LED floodlight is replacing an
existing light and there is no protective earth cable available. First, draw
a new mains cable.
Where the protective earth is not connected, a fault with the mains
voltage might result in the metal housing of the LED floodlight becom-
ing live. There is a risk of a life-threatening electric shock!
When drilling in walls and ceilings, pay attention to cables, gas and
water pipes.
Mounting/Installation
1.
Unscrew the lock nut (5) from the cable gland (4)
and guide the power cable through the lock nut and
the waterproof grommet (6).
2.
Connect the three wires of the power cable with the
lustre terminals.
Operation
10