WARNING
Before using this outdoor fire bowl, make sure you have read, understand and are following all
information provided in the Important Safety Information section of this manual. Failure to
follow those instructions can cause property damage, serious injury or death.
11. CHECKING FOR LEAKS
Make a leak check solution by mixing 1 part dishwashing soap
with 3 parts water in a spray bottle.
Make sure the re bowl control knob is "OFF. " Then, turn the
natural gas on at its source.
Spray leak solution on the valve connections, paying particular
attention to the areas indicated by the arrows.
If any bubbles appear turn the natural gas o at its source,
reconnect and re-test. If you continue to see bubbles after several
attempts, disconnect the natural gas source and contact Real
Flame ® at 1-800-654-1704 for assistance.
If no bubbles appear after one minute, turn the gas
source "OFF", wipe away solution and proceed to next
step.
NOTE: The normal manifold pressure for this converted appliance is 7" water column.
NOTE: The maximum inlet gas pressure for this unit is 10.5 in W.C. (2.61 kPa).
The minimum inlet gas pressure for this unit is 3.5 in W.C. (0.87 kPa).
12.)
Cut the existing French plaque from the control panel using wire cutters. Re-attach
French plaque and NG conversion plaque included with this kit to the fire bowl using
the included cable kit.
Cut Cable
NATURAL GAS CONVERSION
Check for leaks at these locations

Re-attach both plaques

9