Installation, Operation & Maintenance Manual
STEP 2
Test Detector
Access to the interior of the detector, when carrying out any work, must be conducted by a competent person!
Ensure you have the correct gas for the device type prior to application.
Screw and seal the regulator/valve into the gas cylinder outlet.
Once sealed, the regulator pressure gauge will indicate cylinder pressure.
Offer up the applicator hose/cone to the lower vents.
Alternatively, enclose the device and apply gas i.e. in an airtight bag or container.
Open the valve/regulator to allow the gas to be delivered at a pre-set flow rate.
Wait for the device to enter alarm status and energise configured outputs/relays.
At this point...
Remove applicator hose/ cone and turn the gas cylinder regulator/valve off.
Wait for the device to return to normal.
Reset the system.
Record your test details. There is a provision for this in your control panel manual.
End.

Reset Service Message

Access to the interior of the detector, when carrying out any work, must be conducted by a competent person!
It is recommended to bump test detector(s) prior to resetting the service reminder message!

End of Operational Life (EOL)

The EOL is approximate from the first five (5) hours of continuous power!
The EOL will depend on the type of gas your detector is targeting and may vary depending on its application and
environmental conditions such as the frequency of exposure to the target gas, poisons or inhibitors!
The typical life of a gas detector depends on its application and intended target gas, in addition the
operational life can be prolonged if the system and equipment is installed and maintained in
accordance the instructions stated within this manual.
At the end of its predicted operational life – the detector will display an 'End of Life' screen. This message indicates
that the detector has reached its expected operational lifecycle and no gas levels are displayed.
You must contact your supplier immediately for replacement.
IOM Iss: 4 11-21
1.
Carefully remove the detector cover to access the circuit board.
2.
Short out the unmarked service header for ~5s and wait for a 'beep'.
3.
The service message on screen will reset.
Carefully replace the back cover.
4.
Merlin Detector-TFT
13