Mitsubishi Electric CITY MULTI PEFY-AF1200CFM Manuel D'installation
Mitsubishi Electric CITY MULTI PEFY-AF1200CFM Manuel D'installation

Mitsubishi Electric CITY MULTI PEFY-AF1200CFM Manuel D'installation

Masquer les pouces Voir aussi pour CITY MULTI PEFY-AF1200CFM:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

Air-Conditioners
INDOOR UNIT
PEFY-AF1200CFM, PEFY-AF1200CFMR
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
MANUEL D'INSTALLATION
Veuillez lire le manuel d'installation en entier avant d'installer ce climatiseur pour éviter tout accident et vous assurer
d'une utilisation correcte.
All manuals and user guides at all-guides.com
English
Français

Publicité

Chapitres

Table des Matières
loading

Sommaire des Matières pour Mitsubishi Electric CITY MULTI PEFY-AF1200CFM

  • Page 1 All manuals and user guides at all-guides.com Air-Conditioners INDOOR UNIT PEFY-AF1200CFM, PEFY-AF1200CFMR INSTALLATION MANUAL English For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit. MANUEL D’INSTALLATION Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous assurer Français d’une utilisation correcte.
  • Page 2 All manuals and user guides at all-guides.com (Unit: mm [in.]) [Fig. 3.2.1] 1385 (54-9/16) 1325 (52-3/16) (Suspension bolt pitch) 75(3) 1250 (49-1/4) 800 (31-1/2) A Access door B Electrical parts box 600 (23-5/8) C Air inlet D Air outlet E Ceiling surface 1 800 mm [31-1/2 in.] or more 2 100 mm [3-15/16 in.] or more 3 20 mm [13/16 in.] or more...
  • Page 3 All manuals and user guides at all-guides.com [Fig. 7.1.1] [Fig. 7.1.2] A Wrap with a damp cloth to cool A Cut B Remove brazed cap [Fig. 7.1.3] F Insulation pipe (small) (accessory) G Caution: Pull out the insulation on the refrigerant piping at the site, braze the piping, and replace the insulation in its original position.
  • Page 4 All manuals and user guides at all-guides.com [Fig. 7.2.1] Max. 20m [65 ft] 1.5-2 m [5 to 7 ft] Correct piping Max. 300 mm [11-13/16 in.] Wrong piping A Insulation (9 mm [3/8 in.] or more) B Decline (1/100 or more) C Support metal K Air release tube L Trap...
  • Page 5 All manuals and user guides at all-guides.com [Fig. 8.0.1] A Air inlet B Air outlet C Access door D Ceiling surface E Canvas duct F Air filter [Fig. 9.1.1] A Switch 16 A B Overcurrent protection 16 A C Indoor unit D Total operating current be less than 16 A E Pull box [Fig.
  • Page 6 All manuals and user guides at all-guides.com [Fig. 9.3.2] [Fig. 9.3.1] A Terminal block box B Knockout hole A Screw (2pcs) C Remove B Cover [Fig. 9.3.3] A Use conduit to keep the weight of the cable and external force from being applied to the power supply terminal connector.
  • Page 7: Table Des Matières

    • Always use an air cleaner, humidifier, electric heater, and other accesso- 1.2. Precautions for devices that use R410A ries specified by Mitsubishi Electric. refrigerant - Ask an authorized technician to install the accessories. Improper installation by the user may result in water leakage, electric shock, or fire.
  • Page 8: Before Getting Installed

    All manuals and user guides at all-guides.com • Use refrigerant piping made of C1220 (Cu-DHP) phosphorus deoxidized 1.4. Before installation (moved) - copper as specified in the JIS H3300 “Copper and copper alloy seamless electrical work pipes and tubes”. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shav- Caution: ing particles, oils, moisture, or any other contaminant.
  • Page 9: Selecting An Installation Site

    All manuals and user guides at all-guides.com 3. Selecting an installation site • Select a site with sturdy fixed surface sufficiently durable against the weight of 3.1. Install the indoor unit on a ceiling strong unit. enough to sustain its weight •...
  • Page 10: Refrigerant Pipe And Drain Pipe Specifications

    All manuals and user guides at all-guides.com 6. Refrigerant pipe and drain pipe specifications 1 Select the thickness of insulation by pipe size. To avoid condensation, provide sufficient antisweating and insulation to the refrig- erant and drain pipes. Pipe size Insulating material’s thickness When using commercially available refrigerant pipes, be sure to wrap commer- 6.4 to 25.4 mm [1/4 to 1 in.]...
  • Page 11: Drain Piping Work

    All manuals and user guides at all-guides.com 1. Insert the drain hose (accessory) into the drain port (insertion margin: 25 mm Cautions on refrigerant piping [1 in.]). s s s s s Be sure to use non-oxidative brazing for brazing to ensure that no for- (The drain hose must not be bent more than 45°...
  • Page 12: Electrical Wiring

    All manuals and user guides at all-guides.com 9. Electrical wiring 6. Be sure to connect control cables to the indoor unit, remote controller, and the Precautions on electrical wiring outdoor unit. Warning: 7. Put the unit to the ground on the outdoor unit side. Electrical work should be done by qualified contractors in accordance with 8.
  • Page 13: Connecting Remote Controller, Indoor And Outdoor Transmission Cables

    All manuals and user guides at all-guides.com Minimum wire thickness (mm [AWG]) Swtich (A) Breaker for Maximum Model Unit combination Breaker for current leakage wiring (NFB)(A) current (A) Main cable Branch Ground Capacity Fuse PURY-P72THMU(-BS) 5.3 [10] 5.3 [10] 30 A 30 mA or 100 mA 0.1 sec. or less 24.0 Outdoor unit [PURY-P•...
  • Page 14: External I/O Specifications

    All manuals and user guides at all-guides.com 9.4. External I/O specifications Caution: 1. Wiring should be covered by an insulation tube with supplementary in- sulation. 2. Use relays or switches with IEC or equivalent standard. 3. The electric strength between accessible parts and control circuit should have 2750 V or more.
  • Page 15: Consignes De Sécurité

    électrocution ou un pièces que celles spécifiées par Mitsubishi Electric sont utilisées, il y aura un incendie. risque d’incendie ou d’explosion.
  • Page 16: Précautions Concernant Les Appareils Utilisant Le Réfrigérant R410A

    All manuals and user guides at all-guides.com • Demandez conseil à votre revendeur avant de mettre le produit aux rebuts. • N’installez pas l’appareil sur une structure qui pourrait causer des fui- • N’utilisez pas d’additif de détection des fuites. tes.
  • Page 17: Eléments Qui Accompagnent L'appareil Intérieur

    All manuals and user guides at all-guides.com 2. Eléments qui accompagnent l’appareil intérieur L’appareil est livré avec les éléments suivants: Elément N° Accessoires CFMR Elément N° Accessoires CFMR Bride (courte) Notice d’installation Bride (longue) Manuel de fonctionnement Tuyau d’écoulement Rondelle (pour la suspension) Cache de tuyau (pour tuyau d’évacuation) 60 mm [3/8 in.] Ensemble de connecteurs (pour le commutateur de pression statique externe) Cache de tuyau (pour tuyau d’évacuation) 25 mm [1 in.]...
  • Page 18: Installation De L'appareil

    All manuals and user guides at all-guides.com 5. Installation de l’appareil 5.1. Suspension de l’appareil 5.2. Assurer l’emplacement de l’appareil et s s s s s Apporter l’appareil intérieur emballé sur le lieu de son installation. fixer les boulons de suspension s s s s s Pour le suspendre, utiliser une poulie de levage pour le soulever et le s s s s s Utiliser le calibre livré...
  • Page 19: Précautions Concernant La Tuyauterie De Réfrigérant

    All manuals and user guides at all-guides.com 1. Couper la pointe de la tuyauterie de l’appareil intérieur, vider le gaz puis dépo- • N’utilisez jamais les tuyaux de réfrigérant déjà en place. ser le capuchon brasé. - La quantité importante de chlore contenue dans les réfrigérants tradition- nels et l’huile réfrigérante des tuyaux actuels provoquera la détérioration du [Fig.
  • Page 20: Confirmation Des Décharges D'écoulement

    All manuals and user guides at all-guides.com [Fig. 7.2.3] (P.4) 3. Effectuer l’essai de fonctionnement en mode de refroidissement, ou placer le commutateur SWE de la carte à circuit imprimé en position de marche. (La A Appareil intérieur B Isolation (courte) (accessoire) pompe d’écoulement et le ventilateur doivent fonctionner sans télécommande.) C Bride (courte) (accessoire) D Fixation du ruban...
  • Page 21: Câblage De L'alimentation Électrique

    All manuals and user guides at all-guides.com 2. Câbles de la commande à distance Commande à distance MA Commande à distance M-NET Types de câbles Câble gainé à 2 âmes (non blindé) CVV Câble gainé à 2 âmes (non blindé) CVV diamètre des câbles 0,3 à...
  • Page 22: Raccordement Des Câbles De La Commande À Distance Et Des Câbles De Transmission Intérieurs Et Extérieurs

    All manuals and user guides at all-guides.com 5. Lorsque le câblage est terminé, vérifier qu’il n’y a pas de jeu dans les con- 9.2. Raccordement des câbles de la com- nexions et fixer le couvercle au bloc de raccordement en procédant dans l’or- mande à...
  • Page 23 All manuals and user guides at all-guides.com...
  • Page 24 All manuals and user guides at all-guides.com This product is designed and intended for use in the residential, commer- cial and light-industrial environment. Please be sure to put the contact address/telephone number on this manual before handing it to the customer. HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN WT05631X01...

Ce manuel est également adapté pour:

City multi pefy-af1200cfmr

Table des Matières