IMPORTANT: Provide each unit with a single-phase AC un-switched power supply from a 120 V to 347 V circuit used for normal lighting.
PRODUCT DAMAGE WILL OCCUR IF THE RATED INPUT VOLTAGE IS EXCEEDED.
WARNING: During installation of remotes, input wires from main unit to remote units must NOT be connected to each other or connected to
ground. Failure to due so will lead to failure of the main unit.
NOTE: The battery must be connected to the charger board prior to applying AC power to the unit. Battery damage may occur if the battery is
connected longer than 24 hours without continuous AC power provided. See also "Important Battery Information", page 3.
NOTE: The maximum mounting height of EXTL SP640L, SP1100L, SP2200L with tilt and swivel lamp heads is 28.5 feet, 41.4 feet, 62.4 feet
respectively, to meet the minimum illumination requirements of NFPA 101 (current Life Safety Code).
NOTE: Before installation, choose a location that allows adequate clearance for sliding the Rear Housing onto the Mounting Bracket (minimum
6-1/2" above top edge of Bracket)
NOTE: Do not connect battery or power unit until remote units (if applicable) are fully connected and wires are isolated from other potentials
(i.e. remote wires shall be isolated from earth ground).
MOUNTING BRACKET
Universal Mounting Bracket
1
Wall/Ceiling
Mounting
Holes (4)
Mounting
Bayonets (4)
a. Wall/Ceiling mounting-
four (4) 30 lbs. minimum pullout rated fasteners. Mounting surface should be suitable to support 120 lbs.
b. Pole/Column Mounting-
1.
Unistrut Mounting holes for most standard configurations.
Steel Banding Slots for routing around poles and I-beams. (See "Pole Mount Banding "above").
2.
After Mounting Bracket is in place and the conduit is near, slide the enclosure downward onto the Mounting Bayonets (See Figures
2). The enclosure will be in place when the snap-lock feature is engaged in the hole in the Mounting Bracket.
SURFACE CONDUIT MOUNTING
At the top left and both sides of the rear housing, create an
1
appropriate hole using a drill. Attach conduit and secure mounting
plate to wall surface using fasteners with a minimum pullout rating
of 30 lbs. each.
IMPORTANT: prior to drilling out
a hole on the top conduit
location, remove the charger
board assembly to ensure no
damage occurs to the charger
board.
Three drill locations
provided for conduit entry
INSTALLATION and MOUNTING
Locate mounting bracket in desired location using "Wall/Ceiling Mounting Holes" (see Fig. 1). Install using
LIFE SAFETY SOLUTIONS
TEL: 800-705-SERV (7378)
techsupport-emergency@acuitybrands.com
2
Rear housing snap lock
feature works in this
hole
Unistrut
Mounting
®
Holes (4)
Pole Mount Banding
Slots (8)
After creating the opening, remove any shavings or dust
2
from the enclosure, as they may harm the electronic
components or compromise the enclosure seal. Install a
U.L.-listed water-tight fitting appropriate to the installation
into the opening. See Wiring Diagram, page 6. Make
code-approved wire connections to the AC power supply,
and remote lamps (if applicable).
Conduit
openings
www.lithonia.com