5. Programming
For programming the receiver must be connected to the mains. The programming is conserved
during a power failure.
5.1 Programming mode or transmitter deletion mode
N.B.! A transmitter must not be further away than 5 m from receiver in learn mode. The
receiver has a limited range!
To enter the programming mode, short press (approximately 0,5s) the LRN button. This mode
is confirmed by the regular flashing of LED 1.
e) In programming mode, pressing the LRN button again selects the relay output to be
associated with a transmitter (example: if DEL 1 flashes, press LRN, switch to channel
2, LED 2 flashes and LED 1 off).
f) Once the relay output has been chosen, to associate a transmitter, simply press on one
of the switches or press the LRN button (see §6.2). The receiver will acknowledge its
recording in memory by maintaining the LED corresponding to the selected output on for
4 seconds. As soon as flashing LED starts again, another transmitter can be associated
or cleared.
g) To clear a transmitter simply press on one of the switches or press the LRN button of the
desired sensor (see §6.2). The receiver will acknowledge its clearing off the memory by
maintaining the LED corresponding to the selected output off for 4 seconds. As soon as
flashing starts again, another transmitter can be associated or cleared.
h) The association or deletion of transmitters can also be carried out via the UTE
(Universal TEach-in) protocol of EnOcean. A UTE association frame is sent every 3
seconds when the receiver is in programming mode.
To exit programming mode, short press the LRN button. The output is confirmed by the
stopping of regular flashing of the LED(s).
Multiple association programming mode:
This mode is used to associate the 2 relay outputs with a transmitter in a single step.
- To enter the multiple association programming mode, make 3 successive short presses
(<0.5s) on the LRN button. This mode is confirmed by the regular flashing of the 2 LEDs.
Notes:
– No transmitter is programmed in the receiver as supplied state.
– When using BMS products, mono or multi-channel, programming must be performed alone
and channel by channel: you must exit the programming mode between each channel or
select another output, by short press the LRN button and within 5 seconds after the start of
visual acknowledge.
– Up to 32 switch, transmitters and sensors can be allocated to each channel.
– If the memory is full, the receiver exits programming mode upon an additional association
attempt.
– The transmitters are alternatively programmed or cleared in the event of several activations!
– If no button is pressed, learn mode stop automatically after 30 s.
5.2 Clearing off all the programmed transmitters
Press the CLR button for approximately 2s. Clearing is confirmed by the simultaneous lighting
of the 2 LEDs then the regular flashing of LED 1 alone. The receiver returns automatically to
programming mode.
To exit programming mode, short press the LRN button. The output is confirmed by the
stopping of regular flashing of the LED(s).
5.3 Programming for viewing consumption indications
To program the consultation of consumption indications, the 2 channels receiver must be
connected to a suitable software.
5.3.1 Association for consultation
To associate (or disassociate) the receiver with a software suitable for reading consumption
-5-
data, the UTE
(Universal TEach-in) protocol of EnOcean is recommended. Please refer to
§5.1 for association (and disassociation).
5.3.2 Consultation
Consultation of consumption data is possible, after association, in accordance with the EEP
-5-
profile §D2-01-00
:
c)
Have the software send a frame "CMD 0x6 - Actuator Measurement Query" (parameters:
Query energy and Output channel 0x00).
d)
The receiver responds with a "CMD 0x7 - Actuator Measurement Response" frame
containing the consumption data.
5.3.2 Reset consumption data
– Switch off the device.
– Hold down the CLR button, then switch on the device,
– Once the orange LED 1 is fixed, wait for the LED 1 to go red (5s) then release the CLR
button.
– Press the LRN button for about 1s to reset the recorded values of the receiver to zero, the
red LED 1 goes out to confirm the erasure of the data.
-5-
For more details see Communication Profiles – EEP available at:
www.enocean-alliance.org/what-is-enocean/specifications/
TOC2003NUaa_0620
6. Control and functions
Each receiver can receive up to a maximum of 32 transmitters, switches or sensors. Upon
allocating on the selected output the first transmitter or sensor, the operating mode is defined.
The operating mode cannot be changed until all the transmitters have been cleared using the
CLR button.
Switch mode: Each transmitter can be used to change the switching state, of the associated
output of the receiver. It is possible to switch ON (button I) with a switch and OFF (button O) with
another switch.
Window contact mode (D5-00-01): If at least one of the window contacts is open, this
activates ON the associated output of the receiver. If all possible window contacts are closed,
the associated output of the receiver is OFF. The window contacts transmit a signal
approximately every 15 minutes. 60 minutes after receipt of the last signal received, the receiver
considers this contact closed.
6.1 Compatible transmitters
The following transmitters can be associated with the receiver
Designation
Switch
Key card
Windows Handle
Windows contact
Dry contact sensor
-5-
Occupancy Sensor
(*) For more details see Communication Profiles - EEP available at:
www.enocean-alliance.org/what-is-enocean/specifications/
6.2 Transmitter associated functions (switch mode)
The functions associated with different sensors are determined during learning. The learning
process (Cf § 5.1) is to do before activating the transmitter.
Designation
Switch
1
3
1
2
2
4
Key card
Window handle
Window contact
Dry contact sensor
Occupancy sensor
Note *: The ON state corresponds to the lighting of the LED (on the front of the product) and
contact closure output NO.
Note **: The visual acknowledge corresponds to holding the LED on or off for 4 seconds.
6.3 Radio function test (slave)
This RLT function (Radio Link Test, EEP §A5-3F-00
product (master), to perform a radio test range (slave):
a) On the diagnostic product, activate the master RLT mode (refer to its manual instruction)
b) On this receiver, activate the slave RLT mode by a short press (approximately 0,5s) on
LRN and CLR simultaneously. This mode is confirmed by the regular flashing (orange) of
the 2 LEDs.
c) To exit this function, short press (approximately 0,5s) on the LRN button. the output is
confirmed by the stopping of regular flashing of the 2 LEDs. In the absence of test activity,
this function stops automatically after 30 seconds.
0
LINE 10020107:
2
0
LINE reference
2
10020001, 10020019, 10020022
10020067
10020011
10020032, 10020042,10020075
10020047, 10020057
10020051,10020078
Learning
Button 1 (2, 3 ou 4):
Button 1 (2, 3 or 4):
pressed and released before
Transition from ON to
visual acknowledge**
OFF and vice Versa
(Switch mode only §6)
Button 1 (2, 3 ou 4):
Button 1 (or 3): ON
pressed then released after
visual acknowledge**
Button 2 (or 4): OFF
Button 1 (2, 3 ou 4):
Button 1 (2, 3 or 4):
pressed and released before
visual acknowledge** followed by,
pressed then released after
visual acknowledge**
Card inserted before the entry into
Card inserted: ON
learning mode, removed (in
learning mode) then reinserted
Card removed: OFF
Closed to opened or opened to
Tilt to opened: no
closed
change
Opened to tilt: no
change
Closed to opened: OFF
Opened to closed: ON
Press the LEARN button
Magnet away: ON
Magnet near: OFF
Press the LEARN button
Contact closed: OFF
Contact open: ON
Press the LEARN button
Detection (PIR = On):
ON
Detection (PIR = OFF):
OFF
1
) master slave allows, through a diagnostic
EEP Profile*
F6-02-01
F6-04-01
F6-10-00
D5-00-01
D5-00-01
A5-07-01,
A5-07-03
Function obtained*
pressed
: ON
released : OFF
5/6