Start/Stop
s. s . t .
Programmer
-
(0...63)
Reset
r. t .
Programmer
-
-
(0...15)
+8 inverse action
+16 Autoreset enabled (Stop = program reset) (only for
_S.S.t. parameter)
+16 reset from the set it puts into effect them without
zero setting power (only for _ _ rt parameter)
+32 start from current value of process variable
(only for _S.S.t. parameter)
Selection of
sens
probe type for
main input
+8 to enable main input curve 4 point correction
(alternative to custom linearization).
See description in "Main Input Correction Function"
section.
+16 to disable averaging filter on sampled
value (available from software release 3.05)
Note: scale selection with "tYPE" code in InP.
Selection
sns. 2
of probe type
for aux input
+8 to disable averaging filter on sampled value
(available from software release 3.05)
al. n r
Select number of
enabled alarms
bvtt
Function
0
none (key disabled)
1
MAN / AUTO select
2
LOC / REM
3
HOLD
4
Start / Stop self-tuning
5
Start / Stop autotuning
6
Set / Reset outputs OUT 1 ... OUT 4
7
Reset alarms memory
8
-
9
Instantaneous integral reset
10
START / STOP Programmer (if enabled in S.S.t.)
bvt. 2
11
RESET Programmer (if enabled in _ _ r.t.)
+16 disable function in configuration menu
(only for butt parameters)
d.i.F.x Digital input function
Function of
0
d. 1 . f . 1 .
digital input 1
1
(IN1)
2
3
4
5
Function of
d. 1 . f . 2 .
6
digital input 2
7
(IN2)
8
9
10
11
12
+ 16 for inverse logic input
+ 32 to force logic state 0 (OFF)
+ 48 to force logic state 1 (ON)
disp
Defining SV
display function
0
from enabled digital input
1
from AL1 ON
2
from AL2 ON
3
from AL3 ON
4
5
from serial line (address 0049H, bit 0)
6
from serial line (address 0049H, bit 1)
7
from keys
SEnS
Probe type for main input
0
Thermocouple (TC)
1
Resistance Thermometer (RTD)
2
Thermistor (PTC)
3
Voltage 0...50mV / 10...50mV
4
Current 0...20mA / 4...20mA
5
Voltage 0...10V / 2...10V
6
Custom 10V
7
Custom max 50mV
SnS.2
Signal
0
0 ... 1V
1
0.2 ... 1V
2
0 ... 10V
3
2 ... 10V
4
0 ... 20mA
5
4 ... 20mA
6
Potentiometer
~
7
TA 50mA
AL.nr
Alarm 1
Alarm 2
Alarm 3
0
disabled
disabled
disabled
1
enabled
disabled
disabled
2
disabled
enabled
disabled
3
enabled
enabled
disabled
4
disabled
disabled
enabled
5
enabled
disabled
enabled
6
disabled
enabled
enabled
7
enabled
enabled
enabled
+ 8 to enable HB alarm
+ 16 to enable LBA alarm
Function of M/A keys: " "
d.i.F.1, d.i.F.2
none (key disabled)
MAN / AUTO select
LOC / REM
HOLD
Start / Stop programmer
Reset programmer
Software power on/off
Reset alarms memory
Select program 0, 1, 2, 3 (LS bit)
Select program 0, 1, 2, 3 (MS bit)
Advance program to end of cycle
Advance program to last step
Enable program advance
diSP
Lower display (SV) function
0
SSP - setpoint enabled
1
InP.2 - aux input
2
Control output value
3
Deviation (SSP - PV)
Function of "MAN" LEDs: M/A, L/R, ATUN, IN1, IN2 repetition,
led. 1
event programmer, serial port enabled, errors present
LEd.x Function
led. 2
0
1
2
3
4
led. 3
5
6
7
8
9
10
11
12
13
14
15
+ 16 for flashing LED function
bArG
Bargraph
function
Custom linearization for main
Lin
st. 0 0
Step 0
......
st. 3 2
Step 32
(*) Not available for:
16-step programmer (SPPt = 3)
programmer with control parameter groups (SPPt = 2)
input correction function enabled (SEnS + 8)
custom TC input (SEnS = 0; tyPE = 20, 21)
custom RTD input (SEnS = 1; tyPE = 4, 5)
custom PTC input (SEnS = 2 ; tyPE = 2, 3)
CuSt
Set number of parameters
xead
in custom menu
pa. 0 1
Identification code for
parameter 1
......
pa. 1 4
Identification code for
parameter 4
X X X X
The identification code is specified in this
x
position, under the parameter name
U.CAL
U.CAL
1
2
3
4
5
26
LEd.1 (MAN), LEd.2 (AUX), LEd.3 (PRG)
none
MAN/AUTO (ON in manual, OFF in auto)
LOC/REM (ON in remote, OFF in local)
self-tuning enabled
autotuning enabled
IN1 repetition
IN2 repetition
enable serial dialogue
HOLD on
Error present (error code <> 0)
Softstart running
Program 0, 1, 2, 3 (LS bit)
Program 0, 1, 2, 3 (MS bit)
Timer in START
Timer in RESET
Timer RUNNING
bArG
0
Heat
1
Cool
2
Heat + cool
3
PV
4
Aux input (position V2 valve)
5
Current setpoint
6
-
7
-
8
Deviation (PV-setpoint)
10%... + 10% of full scale
• Lin
or aux input (*)
Scale limits
Scale limits
• CuSt
Set custom "dAtA" menu
[ 0 ... 14 ]
• U.CAL
User calibration
Function
Analogue output 1
Analogue output 2
Input 1 - custom probe 10V
Input 1 - custom probe 50mV
Input 2 - potentiometer