3. Wiring

General
The fan and motor specifications are listed on the type-plates.
Max. fuse rating = 13 Amp.
If the fuse is a
Max. short circuit current is 10 kA
At start-up and during the initial adjustment of the fan, it is important to control the
direction of rotation of the motor and to check the motor current does not exceed the
manufacturer's recommended operating current for the motor (to avoid damaging the
motor).
Isolation switch
The isolation switch must ...
Lightning
Any lightning conductor connected to the fan must be in accordance with applicable
conductor
regulations and legislation.

3.1 Fan without EC control

3.1.1 DTH160-4-1, DTH200-4-1
Wiring
Single-phase motor with built-in thermal
cut-out
DTH160-4-1, DTH200-4-1
All single-phase fans are voltage regulated.
The motor is fitted with a thermal cut-out. The thermal-cut out is factory installed, wired
in series to the motor's power circuit.
The wiring must only be done by a qualified electrician.
...it must have the characteristic
melting fuse
gG or gM.
control fuse
B or C, and comply with IEC 90947-2. -
EXHAUSTO A/S would like to draw attention to the fact that, in
accordance with the EU's Machine Directive (appendix 1) all fan
systems shall include a isolation switch.
• be lockable or positioned in plain sight in the immediate vicinity of the fan
• be able to disconnect all poles from the supply voltage
— contact distance of at least 3 mm in each pole
• Set up as isolation switch in accordance with standard IEC 60947-1 or
IEC 60947-3.
The isolation switch is not supplied by EXHAUSTO.
Wiring — cable from the motor
57/77
Brown = L
Blue = N
Yellow/Green =