GB
Installation types
Flush mounting. The power supply unit must be installed in a suitable (mounting) box.
The power supply unit is suitable for installation in European flush-mounted boxes.
Connecting the device
Once all consumers have been successfully connected to the DALI bus, connect the power supply
unit to the 230-V mains. Once the power has been successfully switched on, the DALI bus will
automatically be supplied with power.
Wiring diagram
DALI Power-Supply
DALI Bus
The max. cable length of the DALI bus cable is 300 m when using 1.5-mm² cable. Laying the DALI
bus in combination with the mains cable is not recommended.
Note: The DALI bus is not classified as SELV.