Regulation-control

Publicité

PARAMETER
FEATURE
NUMBER
149
TEMPERATURE LIST
AUXILIARY OAT
150
LIMIT
151
AUXILIARY DELAY
AUXILIARY
152
HYSTERESIS
SANITARY HOT
153
WATER IN OFF
MODE
EXTERNAL HEAT
154
SOURCE STATUS
MAIN WATER PUMP
155
LOGIC VS EHS
STATUS
TRACE HEATER /
156
ADDITIONAL WP
LOGIC
ADDITIONAL WATER
157
PUMP LOGIC
DELTA AIR
158
SET-POINT
The parameters which are read only and are not editable by user, Key pad lock (
value if default value has been changed.
10
DESCRIPTION
This code is use to set which temperature the NUI shall display in temperature
zone.
1. Indoor air temperature
2. Leaving water temperature (from LWT sensor)
3. Entering water temperature (from EWT sensor)
4. Refrigerant temperature (from TR sensor)
5. Suction temperature (from TS sensor)
6. Discharge temperature (from TD sensor)
7. Refrigerant temperature (from TE sensor)
This code is use to set the OAT threshold value under which both the heat pump
and the external heat source will be operative as per algorithm.
This code is use to set the delay time after which, when (temperature set in code
148) < OAT < (temperature set in code 150), the external heat source will switch
on. The counting of the time starts when the activation of the EHS is required as
per algorithm (if current water temperature) < (water temperature set-point –
auxiliary hysteresis)
This code is use to set the hysteresis temperature needed to activate the
external heat source.
logic can be activated:
1. Yes, SHW logic is always actives. If OAT < Par148, Heat Pump will turn ON to
produce SHW.
2. No, SHW logic can be activated only in Heat or Cool mode. No SHW
production when OAT < Par148.
and OAT < temperature value set in Code 148:
0. Always On
set-point (same hysteresis of Thermostat function). Incase of NUI is not installed
hysteresis)
(temperature value set in Code 148):
2. Always On
This code is use to select the output connected at PIN 12 on terminal strip. In case
an additional water pump option is active, this code is use to select its operating
logic vs the SHW request (if OAT > (temperature value set in Code 148).
0. Trace heater installed for the anti frost logic 0 2 1
means that in case of SHW activation, the additional WP will be ON.
always OFF when SHW is activated.
when OAT < temperature value set in Code 148:
2. Always On"
NUI code = 4).
VALUE
RANGE
STANDARD
Min
Max
1
7
1
-20°C
30°C
0°C
1 Min
60 Min
10 Min
1°C
20°C
5°C
1
2
1
0
2
1
0
2
1
0
2
1
0
2
2
0.2°C
1°C
0.3 °C