14.01 FACTORY ASSEMBLED TANK SYSTEMS WITH GUIDE RAIL AND QUICK DISCONNECT DISCHARGE
__
Factory mounted guide rail system with pump suspended by means of bolt-on quick disconnect that is sealed by means of nitrile
grommets. The discharge piping shall be schedule 80 PVC and furnished with a check valve and PVC shut-off ball valve. The tank
shall be wound fiberglass or roto-molded plastic. An inlet hub shall be provided with the system.
__
Stainless steel guide rail
__
Zinc plated steel guide rail
__
" diameter of basin size
__
" height of basin size
__
" distance from top of tank to discharge pipe outlet
__
Fiberglass cover
__
Structural foam polymer cover
__
Steel cover
__
Simplex system with outdoor panel and alarm
__
Separate outdoor alarm
__
Remote outdoor alarm
15.01 TESTING
The pump shall have a ground continuity check and the motor chamber shall be hi-potted to test for electrical integrity, moisture content
and insulation defects. The motor and volute housing shall be pressurized and an air leak decay test performed to ensure integrity of the
motor housing. The pump shall be run, voltage current monitored, and checked for noise or other malfunction.
16.01 QUALITY CONTROL
The pump shall be manufactured in an ISO 9001 certified facility.
17.01 WARRANTY
Standard limited warranty shall be 3 years.
Copyright © Liberty Pumps, Inc. 2019
7000 Apple Tree Avenue Bergen NY 14416
All rights reserved.
Specifications subject to change without notice.
Phone 800-543-2550
Fax 585-494-1839
Email Liberty@LibertyPumps.com
2484LSG_P9 R7/17/2019
Web www.LibertyPumps.com

Publicité

loading

Ce manuel est également adapté pour:

Omnivore 2484lsgx