Télécharger Imprimer la page

Siemens AST10 Mode D'emploi page 12

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 14
Vmin can be adjusted in the range of –20 % ... 100 %
Siemens default setting: Vmin = 0 %
Vmax can be adjusted in the range of 20 % ... 120 %
Siemens default setting: Vmax = 100 %
The setpoint Y can be adjusted in the range of
0.00 V ... 11.00 V
The digitally adjusted setpoint has priority over the analogue
set point.
The analogue setpoint has priority again 60 seconds after
removing the connection between AST10 and
GLB/GDB/ASV181.1E/3.
The actual Air Volume Signal is displayed if U is selected. The
range is from 0.00 V ... 12.8 V and corresponds to an air
volume of 0 % (U = 0 V) to 128.0 % (U = 12.8 V).
GLB/GDB/ASV181.1E's
internal memory
Vn
Section 1
Vmin
(Set Values)
Vmax
Set by AST10,
TYP
ACS931 or ACS941
DIR
Vn
Section 2
Vmin
(Reference Values)
Vmax
Set by ACS931
TYP
DIR
Siemens Building Technologies
74 319 0396 0 c
The GLB/GDB/ASV181.1E/3's internal
memory (EEPROM) contains the parameters
set by the AST10. The memory is split in two
sections.
Section 1:
contains the "Set Values",
that are used for operation
Section 2:
contains the "Reference
Values"
The AST10 allows only to change the
"Set Values".
AST10
B5851
12/34
22.11.2011

Publicité

loading