Instrucciones De Seguridad Para La Instalación Según Ul/Csa - Lenze E94 SHE Single Drive HighLine Série Instructions De Montage

Masquer les pouces Voir aussi pour E94 SHE Single Drive HighLine Série:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

3.4
Instrucciones de seguridad para la instalación según UL/CSA
Original − Inglés
J
Warnings!
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
Type
E94xSxE0324
E94xSxE0474
E94xSxE0594
E94xSxE0864
E94xSxE1044
EDK94SH104 DE/EN/FR/ES/IT 8.0
Instrucciones de seguridad para la instalación según UL/CSA
Branch circuit protection:
– Suitable for use on a circuit capable of delivering not more than
100000 rms symmetrical amperes, 480 V max., when protected by CC, J or
T class fuses.
– Suitable for motor group installation on a circuit capable of delivering not
more than 100000 rms symmetrical amperes, 480 V max., when protected
by class CC, J or T class fuses.
– Use specified fuses as shown in the table.
– Integral solid state short circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with
the National Electrical Code / Canadian Electrical Code and any additional
local codes.
The opening of the branch circuit protective device may be an indication
that a fault current has been interrupted. To reduce the risk of fire or
electrical shock, current−carrying parts and other components of the
controller should be examined and replaced if damaged. If burnout of the
current element of an overload relay occurs, the complete overload relay
must be replaced.
For information on the protection level of the internal overload protection
for a motor load in percent of FLA, see the corresponding Application
Manuals or Software Helps.
For information on rating and proper connection of the thermal protector
(only for connection to motors having integral thermal protection), see the
corresponding Application Manuals or Software Helps.
Max. surrounding air temperature is 45 °C.
Max. surrounding air temperature with derating is 55 °C.
E94xSxE0324 ... E94xSxE0594: Use 60/75 °C copper wire only, except for
control circuits.
E94xSxE0864 ... E94xSxE1044: Use 75 °C copper wire only, except for control
circuits.
Secondary circuit shall supplied from an external isolating source.
These products are intended for use in a pollution degree 2 environment.
These products are intended for use in overvoltage category III.
Branch circuit/short circuit protection with fuses in accordance with UL248
Standard installation
Nominal value (max.) [A]
50
60
60
100
125
l
Instrucciones de seguridad
Motor group installation
Nominal value (max.) [A]
3
125
125
125
300
300
143

Publicité

Table des Matières
loading

Table des Matières