Carrier Comfort Serie Manuel D'utilisation page 8

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 38
Installation
PARAMETER
FEATURE
NUMBER
CDU CAPACITY
136 ( )
EWT SENSOR VALUE
137 ( )
LWT SENSOR VALUE
138 ( )
TR SENSOR VALUE
139 ( )
SYSTEM MODE
140 ( )
DEF MODULE
141 ( )
GMC SOFTWARE
142 ( )
VERSION
GMC SOFTWARE
143 ( )
RELEASE
WATER PUMP
144 ( )
RUNTIME
CURRENT WATER
145 ( )
SET-POINT
146
DRY CONTACT OFF
ALARM / SATISFIED
147
AIR ROOM
TEMPERATURE
EXTERNAL HEAT
148
SOURCE OAT LIMIT
149
TEMPERATURE LIST
AUXILIARY OAT
150
LIMIT
151
AUXILIARY DELAY
8
DESCRIPTION
This code displays the nominal heat pump capacity [kW].
This code displays the Entering Water Temperature read by the EWT
sensor.
This code displays the Leaving Water Temperature read by the
LWT sensor.
This code displays the refrigerant temperature value read by
the TR sensor.
This code displays the operating mode requested by the
System Control:
0. Off
1. Stand by
2. Cooling
3. Heating
4. N.A.
5. N.A.
6. Rating Heating
7. Rating Cooling
8. Freeze Protection
9. Defrost
10. High Temperature Protection
11. Time guard
12. System Fail
13. Advanced Freeze Protection
This code displays the list of the all fault codes detected by the
outdoor unit. If no fault are occurring, no codes will be displayed.
This code displays the GMC Software Version.
This code displays the GMC Software Release.
This code displays the working on hours (x10) of the water
pump.
This code displays the current water set-point defined by the
system control.
This code is use to set the different OFF logics:
1. Standard OFF
2. Controlled Off Cycle (only if HP is controlled by dry contact)
This code is use to select the output connected at PIN 5 on
terminal strip:
1. Alarm signal 1 2 1
2. Signal of reached air temperature set-point
This code is use to set the OAT threshold value under which only the
external heat source will be operative as per algorithm. (Stop HP)
This code is use to set which temperature the NUI shall display
in temperature zone.
1. Indoor air temperature
2. Leaving water temperature (from LWT sensor)
3. Entering water temperature (from EWT sensor)
4. Refrigerant temperature (from TR sensor)
5. Suction temperature (from TS sensor)
6. Discharge temperature (from TD sensor)
7. Refrigerant temperature (from TE sensor)
This code is use to set the OAT threshold value under which both the heat
pump and the external heat source will be operative as per algorithm.
This code is use to set the delay time after which, when
(temperature set in code 148) < OAT < (temperature set in code
150), the external heat source will switch on. The counting of the
time starts when the activation of the EHS is required as per
algorithm (if current water temperature) < (water temperature
set-point – auxiliary hysteresis)
VALUE
RANGE
STANDARD
Min Max
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1
2
1
1
2
1
-20°C 65°C
-20°C
1
7
1
-20°C 30°C
0°C
1
60
10 Min
Min
Min

Publicité

Table des Matières
loading

Table des Matières