Télécharger Imprimer la page

D+H KA 66-SW Notice Originale page 6

Publicité

Les langues disponibles

Les langues disponibles

Intended use
- Chain drive for electric opening and closing of
heavy windows and flaps in the facade and
roof area
- By VdS is the maximum load for one chain at
pressure = 600 mm and at tension = 1000 mm
- Operating voltage 24 VDC
-
U
seable for smoke ventilation, D+H Euro-SHEV
according to DIN EN 12101-2 as well as daily
natural ventilation
- Only for inside mounting
Safety notes
Operating voltage 24 VDC!
Do not connect directly to the mains supply!
- Connection has to be carried out only by an
authorized electrical specialist
- Danger of violent pressure in handaccessible area
- Keep away People from the operating area of the
drive
- Keep away children from the control
- Observe pressure load diagram of the chain
- Use only in dry rooms
- Only for inside mounting.
Use rain detector with danger of rain
(e.g. at domelights or roof windows)
- This product may not be operated without the
covering stoppers, which are delivered with
bracket sets
- Just use unchanged original D+H parts
- Observe mounting instructions of bracket set!
Observe enclosed red safety slip!
Mounting informations
Mount the drive mechanical
stress-free.
With that, more even load
distribution is ensured on all the
drive chains.
6/20
KA 66-SW / KA 106-SW
Performance features
-
M
BSY + for a precise synchronous run
- ndividually programmable (via software SW
I
BSY+)
- SHEV-high speed function (fast-running
feature in OPEN-direction)
- Protection system for the main closing edge
-
P
(only with standard version)
- Locking relief after closing
Pressure load diagram
Observe maximum pressure load of the chain!
Maximum pressure load
automatically identical with maximum pressure force
of the drive!
Extent of supply
Drive unit with 2,5 m silicone cable. Dependent on
the type of window, different bracket sets are
available separately.
At vertical active pulling
application (e.g. for a skylight)
the forces must be rearranged
by software SW-BSY+
English
icroprocessor controlled synchro electronics
ower supply is possible from both sides
500
400
300
200
KA 66-SW
100
KA 106-SW
0
Stroke / (mm)
If after mounting, the measure X
is as bigger as 23 mm, null
balance with software SW-BSY+
is neccesary.
Closure Ranges will shift in
relation to new zero point.
≥ 23 mm ? X
99.823.92 2.2/03/12
per chain
is not

Publicité

loading

Ce manuel est également adapté pour:

Ka 106-sw