The Cube model housing can also be fixed to a wall using the wall-mount tabs (code VAS AE 061). To
achieve this, start by attaching 2 CUBE wall-mount tabs using the paper template (drill holes for the
required orientation of the housing), then attach 4 wall-mount tabs to the housing in the holes
provided for this purpose. Then place the housing in the required orientation and slide the 2 upper
tabs of the housing onto the 2 tabs attached to the wall. The other 2 tabs fitted to the housing act as
stops to hold the housing level:
3.4.3
Free-standing housing
The housing can be free-standing as long as it is positioned for easy access to the filter. You are not
advised to place it on its cover.
Make sure that the support is stable and correctly sized for the weight of the appliance.
3.5

Roof outlet

The roof outlet must be sized for a maximum suction loss of 50 Pa at RS+2 (see 4.9 Initial
settings – Rated speed RS).
The roof outlet must be placed as close as possible to the VMI® housing.
Set the roof outlet up as indicated in its installation and operating manual and according to
the type of roof.
Make sure that it is correctly oriented to prevent rain from entering the duct network.
For air inlets on the building façade:
Bore through the wall following standard practice.
Use a rainproof grille on the outside and optionally an insect grille if it can be accessed to be
cleaned.
Housing Cube
50