seCtIOn 8 |
Model no.
PST-600-12
PST-600-24
PST-1000-12
PST-1000-24
*
NoTES:
1. The ampere carrying capacity (Ampacity) of various sizes of wires is based on NEC Table 310.17
for single, insulated conductors rated at 194˚f / 90˚C insulation, and in free air at 104˚f / 40˚C
ambient. The maximum fuse rating should be equal to or less than the Ampacity of the wire.
2. The wire size is based on allowable ampacity or 2% voltage drop, whichever is thicker.
3. four standard models of Samlex America, Inc. DC Installation Kits are available to cover installa-
tion requirements of 600 to 3500W inverters. Voltage drop of 2% or less will be applicable for
3 ft. (.91 metres) distance. In some cases the kits may contain thicker cables and higher rated
fuses than the minimum sizes recommended. Thicker cables will produce lower voltage drop
and hence, will further improve the overall efficiency. Also, voltage drop may be > 2% in some
cases for distances > 3 ft. (.91 metres).
Dc input connection
The DC input terminals for battery connection (8 & 9 in fig. 6.1) have
cylindrical hole with set screw:
- Hole size for PST-600: 8 mm / .315" with M-8 set screw
- Hole size for PST-1000: 11 mm / .433" with M-8 set screw
Do NoT insert the stranded bare end of the wire directly into the tubular hole as the set
screw will not pinch all the strands, resulting in a partial/loose contact.
To ensure firm contact, a pair of pin type terminal lugs have been provided as follows:
• PST-600: for up to AWG#2 or 35 mm
• PST-1000: for up to AWG#1/0 or 50 mm
Reducing RF interference
Please comply with recommendations given in Section 3 on page 11 - "Limiting Electro-
magnetic Interference".
Ac SiDe connectionS
WARninG! Preventing Paralleling of the Ac output
1. The AC output of the inverter cannot be synchronized with another AC
source and hence, it is not suitable for paralleling. The AC output of the in-
verter should never be connected directly to an electrical breaker panel / load
Installation
Maximum Dc input
current at rated output
power & minimum rat-
ing of external fuse
80A
40A
160A
80A
Size of Wire
0.91M /
1.83M /
3 ft.
6 ft.
AWG #6
AWG #2
AWG #8
AWG #8
AWG #2
AWG #1/0
AWG #6
AWG #6
wire size (Part No. PTNB 35-20)
2
wire size (Part No. PTNB 50-20)
2
Samlex
3.05M /
America Dc
10 ft.
install Kit
AWG #1/0
DC-1000-KIT
AWG #6
DC-1000-KIT
AWG #3/0
DC-2000-KIT
AWG #4
DC-1000-KIT
SAMLEX AMERICA INC. | 33