9 A lack or an excess of refrigerant can cause the unit to stop. Charge the
system with the appropriate amount of refrigerant. When servicing, always
check the information concerning pipe length and amount of additional
refrigerant at the refrigerant volume calculation table on the back of the
service panel and the additional refrigerant section on the labels for the
combined number of indoor units (Refer to item 9.2. for detailed information
0 Charge the system using liquid refrigerant.
a Never use refrigerant to air purge. Always evacuate using a vacuum
pump.
b
a decline in heating/cooling performance, condensation and other such
c When connecting the refrigerant piping, make sure the valve of the heat
it until the refrigerant piping for the heat source unit, indoor units and
BC controller has been connected, a refrigerant leakage test has been
performed, and the evacuation process has been completed.
d Braze only with non-oxided material. Failure to do so may damage the
compressor. Braze using nitrogen purge.
Do not use any commercially available anti-oxidizing agent, because it
may cause pipe corrosion and degrade the refrigerant oil.
Contact Mitsubishi Electric for more details.
e Never perform piping connections when raining.
Warning:
When installing and relocating the unit, do not charge the system with any
- Mixing different refrigerant, air, etc. may cause the refrigerant cycle to
malfunction and result in severe damage.
Caution:
the refrigerant oil.
Do not use the tools shown below used with conventional refrigerant.
(Gauge manifold, charge hose, gas leak detector, check valve,
refrigerant charge base, vacuum gauge, refrigerant recovery
equipment)
- Mixing of conventional refrigerant and refrigerant oil may cause the
refrigerant oil to deteriorate.
- Mixing of water will cause the refrigerant oil to deteriorate.
- R410A refrigerant does not contain any chlorine. Therefore, gas leak
detectors for conventional refrigerants will not react to it.
Manage tools used for R410A carefully.
- If dust, dirt, or water gets in the refrigerant cycle, the refrigerant oil will
deteriorate.
Never use existing refrigerant piping.
- The large amount of chlorine in conventional refrigerant and refrigerant oil
in existing piping will cause the new refrigerant to deteriorate.
Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing.
- If dust, dirt, or water get into the refrigerant cycle, the oil will deteriorate
and the compressor may fail.
Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant to deteriorate.
Do not use special detergents to wash the piping.

9.2. Refrigerant piping system

Example of refrigerant piping system
[Fig. 9.2.1] (P.4, P.6 - 7)
Heat source model
Gas side
Liquid pipe
Model number
Joint
4-Branch header
8-Branch header (Downstream indoor
10-Branch header (Downstream indoor
Heat source twinning kit
A Heat source unit
C Indoor unit
E Heat source twinning kit
*1 ø12.7 for over 90 m [295-1/4in]
*2 ø12.7 for over 40 m [131-3/16in]
*3 The pipe sizes listed in columns A1 to A2 in this table correspond to the sizes
for the models listed in the unit 1 and 2 columns. When the order of the models
for unit 1 and 2 change, make sure to use the appropriate pipe size.
26
Liquid side
Total capacity of indoor units
Gas pipe
Downstream unit model total
B 1st branch
D Cap
F Header
*4 B
*5 C When the height difference between the indoor units is 15 m or greater
[Fig. 9.2.2] (P.5 - 7)
Heat source model
Low-pressure side
Liquid pipe
Model number
Heat source twinning kit
Low-pressure gas pipe
A Heat source unit
C
E
G Heat source twinning kit
*1 When the piping length is 65 m or longer, use the ø28.58 [1-1/8] pipe for the
part that exceeds 65 m.
*2 The pipe sizes listed in columns A1 to A2 in this table correspond to the sizes
for the models listed in the unit 1 and 2 columns. When the order of unit 1 and
2 is changed, make sure to use the appropriate pipe size for the model.
Precautions for heat source unit combinations
Refer to [Fig. 9.2.3] for the positioning of twinning pipes.
[Fig. 9.2.3] (P.8)
<A>
[7-7/8 in] or more.
If there is no trap, oil can accumulate inside the pipe, causing a shortage of
<B>
A
Indoor unit
C
Within 2 m [6 ft]
E
Field-supplied piping
G
Straight pipe length that is 500 mm [19-11/16 in] or more
Precautions for heat source unit combinations
Refer to [Fig. 9.2.4] for the positioning of twinning pipes.
[Fig. 9.2.4] (P.8 - 9)
<A> Install the piping so that oil will not accumulate in the stopped heat source
unit. (both the liquid and the gas side for PQHY-P·TSLMU-A/YSLMU-A, the
1.
The NG example shows that oil accumulates because the units are installed
on a reverse gradient while unit 1 is in operation, and unit 2 is stopped.
2.
The NG example shows that oil accumulates into unit 1 while unit 2 is in
3.
The NG example shows that oil accumulates into unit 1 while unit 2 is in
4.
The NG example shows that oil accumulates into unit 2 while unit 1 is in
<B>
Make sure the slope of the twinning pipes are at an angle within ±15° to the
horizontal plane.
<C>
A
Slope downward
C
E
Slope of the twinning pipe is at an angle within ±15° to the ground
F
H
Field-supplied piping (low-pressure connecting pipe: between heat source
I
J
Caution:
failure.
start-up failure.
Do not install a sight glass because it may show improper refrigerant
If a sight glass is installed, inexperienced technicians that use the
glass may overcharge the refrigerant.
High-pressure side
Total capacity of indoor units
Gas pipe
Downstream unit model total
High-pressure gas pipe
B
D
F
B
D
Twinning pipe
F
Twinning kit
B
Slope upward
D
Twinning pipe
G