WARNING
Before servicing or cleaning unit, switch power off
at service panel and lock the service disconnecting
means to prevent power from being switched on
accidentally. When the service disconnecting means
cannot be locked, securely fasten a prominent
warning device, such as a tag, to the service panel.
Cleaning and Maintenance
To Clean
For quiet and efficient operation, long life and attractive
appearance, remove Grille and vacuum interior of unit
with a dusting brush attachment.
The Motor is permanently lubricated and never needs
oiling. If the motor bearings are making excessive or
unusual noises, replace the Control Assembly and Motor.
Troubleshooting
Problem
The fan does not run
The fan runs erratically Check that the Blower Wheel is firmly attached to the Motor shaft and both spin freely.
The fan seems noisy
The fan does not
properly ventilate the
room
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
Greenheck SP/CSP catalog provides additional information
describing the equipment, fan performance, available
accessories, and specification data.
®
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
12
SP Ceiling Exhaust/Inline Fans, Rev. 3, November 2013
Potential Solution
Check for an open fuse or circuit breaker in the building's service panel.
Check that the two (2) plug-in connections for the Motor and the Control are seated
firmly in place.
Check that the Blower Wheel spins freely.
Check that the back draft damper in the fan's Duct Connector pivots freely. Screws used
to attach the duct to the Duct Connector may be preventing the damper from opening.
Check that the back draft damper in the wall or roof cap pivots freely. These dampers
are sometimes mistakenly painted shut or obstructed by bird and insect debris.
For spot ventilation, turn both the master switch and the mode select switch ON to
enable the fan to run at the certified airflow rate.
For spot ventilation followed by continuous ventilation, increase the "TIME" setting of the
user-adjustable time delay.
For continuous ventilation, increase the "CFM" setting of the user-adjustable airflow rate.
To Change Bulbs
Refer to Retrofit Installation Step 14 (page 11).
1. Carefully insert a small
flathead screwdriver
between the Grille and
Lens, then twist to
remove Lens.
2. Purchase two (2) 18W
(max.) type GU24
fluorescent lamps with
Maximum Overall Length
(MOL) of 3.9" (100 mm).
Purchase a 4W (max.)
C7-type incandescent night light bulb.
3. Insert bulbs into their sockets. Replace Lens.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be obtained
from AMCA International, Inc. at www.amca.org.