FlowJet-60
Unwrap hose from unit. Attach to output of pump.
Attach spray gun to quick connect on hose.
Unwrap power cord from unit. Plug into appropriate outlet. Test and reset GFCI.
Attach water supply hose to unit (2.5 gallons per minute minimum). Make sure screen
washer is in place.
Turn on water. To prime the pump, squeeze the spray gun trigger until water exits nozzle for
3 seconds.
Normal Coil Cleaning
Attach yellow cleaning nozzle (size 1508) to spray gun.
While holding spray gun trigger open, flip power switch (rear of unit) to "ON" position.
Spray condenser with plenty of water to remove loose debris.
Remove yellow cleaning nozzle.
Attach black cleaning nozzle (size 2540).
Make sure chemical pickup hose is in chemical container and the tip is at the bottom.
Apply water/chemical solution evenly to coils (siphon ratio is approximately 10:1).
Allow chemical to dwell on coil per manufacturer's recommended time.
Remove black soaping nozzle, attach yellow cleaning nozzle, and thoroughly rinse coils
with clean water.
When done, flip power switch to the "OFF" position and relieve pressure in hose.

General Maintenance and Storage

If using with coil cleaning chemicals, run clean water through the pump when done.
Store unit indoors.
IMPORTANT! Replace water seals immediately if pump leaks between head and crankcase.