You want your generator to be ready when you need it -- so, it is important to perform the following steps once a month:
Start and run generator power through your transfer switch circuits.
Keep your fuel tank filled with fresh fuel.
With your Reliance Controls Easy/Tran TF installed, it is not necessary to turn off any of your load center breakers when starting
your generator, even when utility power is fully functional. This is because the double throw break-before-make action of the furnace
relay prevents feeding generator power to the utility and, conversely, prevents feeding utility power back to your generator.
A. Transferring from Utility Power to Generator Power in an Emergency
1.
Make sure that the toggle switch on the Easy/Tran TF is in the LINE position.
2.
Plug the appropriate extension cord into the appropriate receptacle on your generator.
3.
Plug the female end of the extension cord into the power inlet box.
4.
Start your generator outdoors and let it warm to a point where it is running evenly.
5.
Turn the toggle switch on the furnace relay to the GEN position.
B. Transferring back to Utility Power When the Power Is Restored
1.
Move the toggle switch on the Easy/Tran TF back to the LINE position.
2.
Turn off your generator.
3.
Unplug the extension cord.
Maximum Watts
Maximum Combined Load @ 125 Volts AC (Amps)
Maximum Load per Circuit from Generator (Amps)
Maximum Load per circuit from Load Center (Amps)
Wattmeters
Number of Knockouts Available 1/2" or 3/4"
Cabinet Dimensions H x W x D (inches)
Cabinet Type (NEMA)
Reliance Controls Corporation ("Reliance") warrants this Protran® Manual Transfer Switch ("Switch") to be free from failure to perform as
intended due to defects in materials and workmanship for a period of five (5) years from date of manufacture, provided the Switch has been
installed and used in accordance with manufacturer's instructions and has not been subjected to misuse, alteration, accident, or repair not
performed by Reliance. If, within such warranty period, the original purchaser gives written notice to Reliance at the address shown below and
the Switch has been proven to Reliance's reasonable satisfaction to be defective, then Reliance at its sole option shall either: (i) supply a
replacement component(s) for the defective component(s) or (ii) repair or replace the Switch. Reliance's obligation is strictly limited to said
repair or replacement of the Switch and Reliance shall not be liable for any incidental, special or consequential damages. The cost of labor to
remove or install a replacement component or Switch is not included in this warranty. The foregoing warranty is exclusive and in lieu of all
other expressed or implied warranties, if any, including but not limited to implied warranties of merchantability and fitness for a particular
purpose. Reliance strongly recommends that the purchaser seek the advice of a licensed electrician to determine the suitability of this product,
and for its proper installation in accordance with all applicable state and local building codes. This warranty gives you specific legal rights, and
you may have other rights which vary from state to state.
OPERATING INSTRUCTIONS
SPECIFICATIONS
Five Year Limited Warranty
TF151 & TF151W
TF201 & TF201W
1875
15
15
20
No
2
7 1/2" x 7" x 4 1/2"
1
2500
20
20
20
No
2
7 1/2" x 7" x 4 1/2"