Acson 5MSY18BR Manuel D'installation page 7

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 14
INSTALLATION OF THE OUTDOOR UNIT (5MSY18BR)
• Where a wall or other obstacle is in the path of outdoor unitʼs intake or exhaust airfl ow, follow the installation guidelines
below.
Wall facing one side
More than 50
Side View
• Do not install the unit at altitude over 2000m for both indoor and outdoor
• Before installing the piping and connecting cord, please remove the plastic valve cover for easy access. Refer to fi gures
shown below.
Drain work (Heat Pump Unit Only)
1) Use drain plug for drainage.
2) If the drain port is covered by a mounting base or fl oor surface, place
additional foot bases of at least 30mm in height under the outdoor
unitʼs feet.
3) In cold areas, do not use a drain hose with the outdoor unit. (Otherwise,
drain water may freeze, impairing heating performance.)
More than 100
More than 50
! CAUTION
PLEASE REMOVE
PLASTIC VALVE
COVER WHEN
CONNECTING
THE PIPING AND
CONNECTING
CORD.
PUSH & PULL UP
1-5
Wall facing two sides
More than 100
More than 150
Top View
Wall facing three sides
More than 150
More than 300
More
than 50
Top View
Bottom frame
Drain Plug
Hose (available comercially,
inner dia. 16mm)
More than 50
Unit : mm
Drain water hole

Publicité

Table des Matières
loading

Table des Matières