Product Certification; Pre-Installation - Thermon Norseman XB Serie Instructions D'installation, D'utilisation Et D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

A.

PRODUCT CERTIFICATION

Depending on the particular model ordered, the heater is
suitable for the following areas:
CSA C/US certified for Class I, Div. 1 and 2, Groups A, B,
C, and D; Class II, Div. 1 and 2, Groups E, F, and G; Class III,
Div. 1 and 2; Temperature Code T2D, T3B, T4A or T6. CSA
type 4, Class I, Zone 1 and 2, Groups IIA, IIB and IIC.
NOTE:
Heaters marked with temperature code T2B are
not suitable for Class II and Class III applications.
Operating ambient temperature:
Standard XB Models: -50°C to 40°C
High Ambient XB Models: -50°C to 70°C
B.

PRE-INSTALLATION

1.
Initially, inspect the heater for possible damage due to
shipping and handling. Claims for shipping damages
shall be placed with the carrier.
2.
Check the heater nameplate to ensure that the heater
area classification and temperature code are suitable
for the hazardous area classification. For details of
hazardous locations with potential for explosion, refer
to the Canadian Electrical Code or National Electrical
Code.
3.
Check to ensure that the heater voltage is the same
as the supply voltage
4.
The heater must be installed by qualified personnel
in strict compliance with national and local electrical
codes.
WARNING. Do not connect the heater to an
electrical supply voltage other than that shown on
the product nameplate.
WARNING
3

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Norseman xb1Norseman xb2Norseman xb3Norseman xb4

Table des Matières