ABB CP-ASI/2.8 Instructions De Montage Et De Mise En Service page 15

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 10
Technical data
o
Data at T a = 25
C, U in = 230 V AC and rated values, unless otherwise indicated
Type
Input circuit
Rated input voltage U
in
Input voltage range
Frequency range AC
Typ. input current
Typ. power consumption
Inrush current limiting / I²t (cold start)
Discharge current towards PE
Power failure buffering time
Transient overvoltage protection
Internal input fuse
External fusing (not necessary, but recommended)
Power Factor Correction (PFC)
Output circuit
Rated output power
Rated output voltage
Tolerance of the output voltage
Rated output current I
r
Derating
Signalling contact for ground fault
Control time
Starting time after applying supply voltage
Rise time
Residual ripple
Switching peaks
Output circuit - No-load, overload and short-circuit behaviour
Characteristic curve of output
Short-circuit protection
Short-circuit behaviour
Current limiting at short circuit
switch position 115 V
switch position 230 V
switch position 115 V
switch position 230 V
switch position 115 V
switch position 230 V
at 100 V AC
at 120 V AC
at 132 V AC
< 20 A /
at 220 V AC
at 230 V AC
at 240 V AC
at 264 V AC
< 38 A /
at 115 V AC
at 230 V AC
at 250 V AC
at 120 V AC
at 230 V AC
at T a < 60 °C
60 °C < T a < 70 °C
11-12
BW = 500 kHz
BW = 20 MHz
min/max
CP-ASI/2.8
100-120 V AC
220-240 V AC
184-264 V AC
184-264 V AC /
240-300 V DC
2.0 A
0.9 A
94 W
< 44.7 A / 3.7 A²/s
1.5 A²/s
< 49.3 A / 4.6 A²/s
< 49.7 A / 2.5 A²/s
1.8 A²/s
< 57.5 A / 3.3 A²/s
min. 35 ms
min. 40 ms
2.5 A slow-acting
3.15 A slow-acting
circuit breaker with C characteristic min. 6 A,
or alternatively 10 A with B characteristic
0.58
0.53
+, -
85 W
2.8 A
2.5 % per Kelvin temperature increase
n/a
max. 25 V AC or
60 V DC, 0.5 A
max. 400 ms
max. 700 ms
typ. < 50 mV
typ. < 100 mV
typ. < 150 mV
pp
U/I characteristic curve
continuous short-circuit stability
continuation with output power limiting
3.2 A / 4.6 A
CP-ASI/4.0
CP-ASI/8.0
L, N
85-132 V AC
184-264 V AC
47-63 Hz
2.7 A
1.3 A
135 W
< 12 A /
< 14 A /
< 24 A /
< 27 A /
< 3.5 A
min. 40 ms
min. 20 ms
min. 40 ms
min. 30 ms
varistors
8 A slow-acting
11, 12, +, -
122 W
30.5 V DC
± 3 %
4.0 A
< 2 ms
max. 500 ms
max. 100 ms
pp
typ. < 100 mV
pp
combined U/I
characteristic curve
and hiccup mode
temporary short-circuit
4.2 A / 6.5 A
12 A / 25 A (max. 5 s)
6.0 A
2.8 A
261 W
1.0 A²/s
1.5 A²/s
1.4 A²/s
1.6 A²/s
0.53
0.48
+, -
244 W
8.0 A
n/a
pp
stability
15