Télécharger Imprimer la page

Siemens 3VL21-KN30 Serie Instructions De Service page 12

Publicité

DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying
this device before working on this device.
1
3
" A"
Wire Connector
Wire Connector
[ Conexión
[ Conexión
del cable ]
del cable ]
8 mm
8 mm
8 mm
OR
OR
OR
5/16"
5/16"
5/16"
TAW1FG350 / 3VL9335-4TD01
TAW1FG350 / 3VL9335-4TD01
3TAW 1FG350 / 3VL9335-4TD31
3TAW 1FG350 / 3VL9335-4TD31
12 / 15
PELIGRO
!
Tensión peligrosa.
Puede causar la muerte o lesiones graves.
Desconectar la alimentación eléctrica antes
de trabajar en el equipo.
Req. Wire Stranding
Req. Wire Stranding
Wire Size
Wire Size
[ Rango Cable ]
[ Rango Cable ]
CU / AL
CU / AL
Class B
Class B
Cu / Al
Cu / Al
7 STRANDS
7 STRANDS
4 AWG
4 AWG
Cu / Al
Cu / Al
3 – 1 AWG
3 – 1 AWG
7 STRANDS
7 STRANDS
[ 25 - 35 mm² ]
[ 25 - 35 mm² ]
Cu / Al
Cu / Al
19 STRANDS
19 STRANDS
1/0 – 4/0 AWG
1/0 – 4/0 AWG
[ 70 – 95 mm² ]
[ 70 – 95 mm² ]
250 - 350 kcmil
250 - 350 kcmil
37 STRANDS
37 STRANDS
[ 120 - 150 mm
[ 120 - 150 mm
2
2
]
]
!
Tension électrique.
Danger de mort ou risque de blessures graves.
Mettre hors tension avant d'intervenir sur
l'appareil.
FG
2
UL 486A - 486B
UL 486A - 486B
( Cable )
( Cable )
CU
CU
Class C
Class C
19 STRANDS
19 STRANDS
19 STRANDS
19 STRANDS
37 STRANDS
37 STRANDS
61 STRANDS
61 STRANDS
DANGER
CLICK
Torque
Torque
[ esfuerzo de torsión ]
[ esfuerzo de torsión ]
150 lb.in.
150 lb.in.
[ 17 Nm ]
[ 17 Nm ]
200 lb.in.
200 lb.in.
[ 23 Nm ]
[ 23 Nm ]
275 lb.in.
275 lb.in.
[ 31 Nm ]
[ 31 Nm ]
Bestell-Nr. / Order No.:3ZW1012-0VL00-0AA0
Wire
Wire
Strip
Strip
Length
Length
[ Quitar ]
[ Quitar ]
"A"
"A"
"A"
.87"
.87"
[ 22 mm ]
[ 22 mm ]

Publicité