No: 25097 – 10/16 rev. 1
Catalog Number • Numéro de Catalogue • Número de Catálogo: LMPB-100
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
Installation shall be in accordance with all applicable
regulations, local and NEC codes. Wire connections shall be rated
suitable for the wire size (lead and building wiring) employed.
For Class 2 DLM devices and device wiring: To be connected to a
Class 2 power source only. Do not reclassify and install as Class 1,
or Power and Lighting Wiring.
MOUNTING IN AN LMZC-301
NOTE: The LMZC has two DLM Local Networks (A and B).
If installing only a single LMPB-100, connect LMRJ
cable to only a single network.
Knock out for mounting a second LMPB-100
ATTACHING LMRJ CABLES
Remove rubber jack cover. If connecting to an LMZC-301,
connect to only one network. Leave covers for unused jacks
in place.
Wattstopper
DLM – Network Power Booster
Gestion numérique de l'éclairage – Amplificateur de puissance réseau
Control de la iluminación digital – Impulsor de alimentación de red
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Input Voltage ...................................... 120/230/277VAC, 50/60Hz
Output ............................................................... 150mA @ 24VDC
Connection to the DLM Local Network .................... 3 RJ-45 ports
DLM Local Network characteristics when using LMRC-11x/2xx
room controllers:
Low voltage power provided over Cat 5e cable (LMRJ);
max current 800mA. Supports up to 64 load addresses,
48 communicating devices including up to 4 LMRC-10x
series and/or LMPL-101 controllers.
Free topology up to 1,000' max.
Environment ................................................. For Indoor Use Only
Operating Temperature .................32° to 140°F (0° to 60°C)
Storage Temperature ...................23° to 176°F (-5° to 80°C)
Relative Humidity .......................5 to 95% (non condensing)
Patent #8487474
WIRING IN AN LMZC-301
The drawings below show wiring for 120V. For 277V, connect the
black (line) wire to the terminal furthest to the right.
Wiring for an LMPB-100
Green (Ground)
White (Neutral)
Black (Line)
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
MOUNTING AND WIRING TO A JUNCTION BOX
The LMPB-100 power boster can either be mounted external to a
junction box (placing it in the plenum space), or mounted directly
inside a 4" x 4" junction box.
Outside a 4" x 4" box
®
SPECIFICATIONS
Wiring for two LMPB-100s
Green (Ground)
White (Neutral)
Black (Line)
J-Box
Inside a 4" x 4" box
J-Box

Publicité

loading

Sommaire des Matières pour LEGRAND Wattstopper LMPB-100

  • Page 1 Wattstopper ® DLM – Network Power Booster Gestion numérique de l’éclairage – Amplificateur de puissance réseau Control de la iluminación digital – Impulsor de alimentación de red No: 25097 – 10/16 rev. 1 Installation Instructions • Instructions d’Installation • Instrucciones de Instalación Catalog Number •...
  • Page 2 CONNECTIVITY The LMPB-100 provides low voltage power LMSW-105 LMDM-101 to DLM devices connected to the DLM Local LMPB-100 Scene Switch Dimming Switch 120/230/277VAC Power Network. Connection drawings are for Booster example only. The low voltage LMRJ cables LMRJ Cables can connect to any DLM device with an open RJ-45 receptacle.
  • Page 3 MONTAGE ET CÂBLAGE SUR UNE BOÎTE DE JONCTION L’amplificateur LMPB-100 peut être installé à l'extérieur d'une boîte de jonction, placé dans le plafond technique ou être installé directement dans une boîte de jonction de 10 x 10 cm (4 x 4 po) J-Box J-Box Hors d’une boîte de...
  • Page 4 No. 25097 – 10/16 rev. 1 © Copyright 2016 Legrand All Rights Reserved. 800.879.8585 © Copyright 2016 Tous droits réservés Legrand. www.legrand.us/wattstopper © Copyright 2016 Legrand Todos los derechos reservados.