CLCM1T,2T,4T,5T,6T WALL MODULES – INSTALLATION INSTRUCTIONS

Mounting Procedure

1. Disassemble the cover as shown in Fig. 1.
2. CLCM2T,4T,5T,6T, only: Pull off the setpoint dial.
3. Mount the wall module onto the wall outlet box, or bore
wall holes as specified in Fig. 2 and mount the wall
module with appropriate screws.
4. Connect the wires to the terminal block according to
section "Wiring".
5. CLCM2T,4T,5T,6T, only: Insert the setpoint dial and turn
it clockwise as far as possible.
6. CLCM2T,4T,5T,6T, only: Make sure that the dial's
position is such that the 30 (°C absolute scale) or the +5
(°C relative scale) points to the right-hand side of the wall
module (see Fig. 3).
Fig. 3. Mounting position of setpoint dial
7. CLCM2T,4T,5T,6T, only: If the dial does not have the
correct position, pull the dial off again and reinsert it with
the correct orientation.
8. Remount the cover as depicted in Fig. 1 and make sure
that the tab on the underside engages.
Wiring
TERMINAL
BLOCK
Fig. 4. CLCM1T,2T – mother board
FAN SWITCH
(CLCM5T,6T, only)
JUMPERS
1: W77xx
2: W7753
3: XL500
TERMINAL
BLOCK
Fig. 5. CLCM4T,5T,6T – mother board
MU1Z-0901GE51 R0416B
SETPOINT
(CLCM2T, only)
BYPASS
OVERRIDE
BUTTON
A B
1: W77xx
2: W7753
3: XL500
SETPOINT
Wiring with PANTHER
NOTE: You should always first connect the wall module and
only then install the PANTHER's software.
Wire the terminal blocks as follows:
1. Strip 5 mm of insulation from the conductor.
2. Insert the wire in the required terminal location and
tighten the screw to complete the termination.
3. Verify wall module wiring with Table 3 or Table 3 and
jumper setting with Fig. 6.
IMPORTANT
Screw-type terminal blocks are designed to accept no
more than one 1.5 mm
Table 2. CLCM1T,2T terminal connections (PANTHER)
wall module
terminal
1
sensor
setpoint (not internally
2
connected)
3
common
Table 3. CLCM4T,5T,6T terminal connections (PANTHER)
wall module
terminal
1
common / ground
2
sensor
3
setpoint
4
bypass / fan
LED (reserved for connection
5
to a 4...20 Vdc, 3.5 mA input)
6
bypass / rtn
7
LED / rtn
When all wiring is complete, re-attach the cover of the wall
module as shown in Fig. 1 and make sure that the tab on the
underside engages.
Jumper Setting with PANTHER
The jumper setting of the CLCM4T,5T,6T with the PANTHER
LED
is shown in Fig. 6.
Fig. 6. Jumper setting of CLCM4T,5T,6T (PANTHER)
2
conductor.
2
function
function
1: W77xx
1: W77xx
2: W7753
2: W7753
3. XL500
3. XL500
PANTHER
terminal
See COACH
print-out.
PANTHER
terminal
See COACH
print-out.
n.a.
n.a.
n.a.