Configuration avec WRD + WBM + WRM30
Liste affichée:
WRM30
n.1
SETUP:
|
|
VEoCharge:
14.40V
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
VLowBatte:
12.56V
|
|
|
|
VEndLBatt:
auto
|
|
|
|
|
|
Prog.Load:
16hour
|
|
|
|
|
|
VnightThd:
2.00V
|
|
|
MPPT algo:
auto
|
|
|
HrToFloat:
1hour
|
|
UPDATE FW:
---
Manuel utilisateur
(1..8)
Valeur:
Valeur réglable et descriptions:
<1..8> select the WRM30 to edit.
Set the battery charge voltage:
Pb Flood
Setting to operate with Pb Flood type
battery.
Pb Seal/Gel
Setting to operate with Pb Seal or Gel type
battery.
LiFePO4
<14.00..14.70V>
<28.00..29.40V>
<56.00..58.80V> fixed :
Setting to operate with Lithium type battery
with integrated BMS.
<12,00..12,56V> / <24,00..25,12V> / <48,00..50,24V> :
below this threshold, the WRM30 goes into
Low Battery status and deactivates the LOAD.
auto(VEoC-0,2/0,4/0,8V);
<12,72..13,68V> / <25,44..27,36V> / <50,88..54,72V> :
above this threshold, the WRM30 goes out
Low Battery status and reactivates the LOAD.
24h/24h
<1..16h>
Only Night: LOAD active only during the night.
Only Day
OnSurPlus : LOAD active only during an energy surplus.
2,00V; 3,28V; 4,56V; 5,84V : below this threshold, the
WRM30 detect the sunset.
auto; parall.; indep. : mode in which the MPPT
algorithm considers the two channels.
<1..8h> : time in Absorption phase before moving to
RUN : *CAUTION* starts the procedure to update the
firmware in the WBM device. The firmware update
file must be present in the uSD card.
WRD
14.80@25°C / 29.60@25°C / 59.20@25°C :
1
14.40@25°C/ 28.80@25°C / 57.60@25°C :
1
1
: LOAD always active.
: LOAD active from sunset for the set hours.
: LOAD active only during the day.
1
Float phase.
18
MENU 8.2