6�7�2 Dehumidification Enabling Signal From Water; Probe; Alarms - Daikin FWTOUCH Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

the fan (and valve, if present) will be activat-
ed even if the room temperature has already
reached the programmed set-point (indicated
on the display). Should the room temperature
fall too far below this threshold, the logic will be
temporarily inhibited.
6.7.2 Dehumidification enabling signal
from water probe
Enabling of the dehumidification function is tied

6.8 ALARMS

The alarms managed by the controller and indi-
cated on the display are as follows:
Ū Air probe alarm
Ū Water probe alarm
Ū Humidity probe alarm
Ū Minor alarm from ID (caused by closing the
ID4 input)
Ū Serious alarm from ID (caused by closing the
ID5 input)
Ū PLC connection alarm (caused by loss of the
connection of the display to the board)
16
FWTOUCH
to the water temperature. The related enabling
logic is described below:
If enabling conditions do not exist, the dehu-
midification function will be temporarily inhib-
ited. The same will occur in the event that the
probe is disconnected.
INFO:
Once the target level of humidity is
reached or the controller is switched OFF, de-
humidification will be disabled.
Water probe alarm

Publicité

Table des Matières

Dépannage

loading

Table des Matières