2. The bonding must be accomplished by using a
solid copper conductor, No. 8 AWG or larger. In
Canada No. 6 AWG or larger must be used. Bond
the motor using the external bonding lug provided
on the motor frame.
WARNING
Always disconnect the power source before working
on a motor or it's connected load.
WARNING
Make sure that the control switch, time clock, or
control system is installed in an accessible location,
so that in the event of an equipment failure or a loose
plumbing fi tting, the equipment can be turned off. This
location must not be in the same area as the pool
pump, fi lter, and other equipment.
CAUTION
The pump must be permanently connected to a
dedicated electrical circuit. No other equipment,
lights, appliances or outlets may be connected to the
pump circuit, with the exception of devices that may
be required to operate simultaneously with the pump,
such as a chlorinating device or heater.
Breaker Panel
GROUND
GFCI
Figure 4.
Bonding the Motor

3.2.3 Electrical Wiring

1. The pump motor must be securely and adequately
grounded using the green screw provided. Ground
before attempting to connect to an electrical power
supply. Do not ground to a gas supply line.
2. Wire size must be adequate to minimize a voltage
drop during the start-up and operation of the pump.
3. Insulate all connections carefully to prevent
grounding or short-circuits. Sharp edges on
terminals require extra protection. For safety,
and to prevent entry of contaminants, reinstall all
conduit and terminal box covers. Do not force
connections into the conduit box.
Pro Series VS PlusHP Pumps
®
Bonding Lug
Terminal Block
Pump
|
Installation & Operation Manual

3.2.4 Controller Options

The pump can be operated by one (1) of four (4)
controllers,
JEP-R variable-speed controller, AquaLink RS,
AquaLink PDA or AquaLink Z4.
The pump communicates with the controllers via a four-
wire RS-485 interface.
NOTE Since the pump is operated by an external
controller the pump will not be turned on until it
is turned on with a controller.
3.2.4.1 Install with AquaLink
The VS PlusHP pump can be operated by the following
AquaLink Controllers:
• AquaLink RS
• AquaLink PDA
• AquaLink Z4
1. Disconnect the high voltage lines or open any
breaker to which the pump power is connected.
ELECTRICAL SHOCK HAZARD
Turn off all switches and the main breaker in the
variable-speed pump electrical circuit before starting
the procedure. Failure to comply may cause a shock
hazard resulting in severe personal injury or death.
2. Dip switches 1 and 2 need to be in the OFF
position. See "Figure 5. Wiring AquaLink RS,
PDA or Z4".
3. Select the desired address(es) by setting dip
switches 3 and/or 4, as shown in "Table 2. Dip
Switch Settings"
4. Disconnect the RS-485 cable from the 4-pin
header on the pump drive.
NOTE: Do not cut the cable or you will lose the ability to
return to the default factory confi guration
5. Connect the new RS-485 cable from the AquaLink
through the available compression fi tting and
route the 4-conductor cable through the motor
drive threaded port closest to the connector. See
""Figure 5. Wiring AquaLink RS, PDA or Z4"
6. Connect the other end of the cable to an RS-485
connector on the AquaLink RS (or multiplexer
interface board), matching wire colors with
connector positions See "Figure 5. Wiring
AquaLink RS, PDA or Z4"
7. Restore power to the pump and verify the
operation of the controller.
8. Refer to the appropriate manual for set up and
operation of the pump:
• AquaLink RS Manual #6593
• AquaLink PDA Manual #H0572300
• AquaLink Z4 Manual #H0386600.