Detnov CCD-108 Manuel D'installation Et Mode D'emploi page 60

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Connecting/disconnecting the sounders output:
The sounders are connected and disconnected by using the sounder silence and
activation keys:
With the sounders connected and on standby, if you press the sounders silence key,
the sounders will be disconnected.
With the sounders disconnected, if you press the activate sounders key, the sounders
will be connected.
GB
6.4.5- Test mode
This operation mode is designed for the maintenance of the installation. The unit is in
this mode when one of the zones is in test mode. This mode is indicated as follows:
General test indicator: activated, blinking.
Active test zone indicators: The indicator corresponding to the zone in test mode
will blink.
In this operation mode, any alarm caused in the test zone will be reflected in the unit
for 3 seconds. After this time the unit will automatically be reset.
Configuring the test mode:
A zone in test mode is configured by pressing the key of the zone you wish to put into
test mode. To take a zone out of test mode, do the following:
Press the button of the corresponding zone: test mode is activated.
Press the general test button: test mode is deactivated.
6.4.6-Out of service mode
The unit is out of service when there is no mains power supply and the batteries are
operating at below 22V. In this state the panel will not indicate any type of event that
may occur in the system; it will not detect alarms or faults. The indication that the unit
is out of service is the following:
General fault warning activated intermittently.
Out of service warning activated continuously.
Acoustic warning activated continuously.
Fault output activated.
24

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ccd-100Ccd-102Ccd-104Ccd-112

Table des Matières