Les langues disponibles

Neon Bulb
Left LED
61-086
61-086 only
Neon Bulb
Left LED
Continuity
Off
On
Open
Circuit
No Voltage
Off
Off
6-65 AC
Off
On
6-90 DC
Off
On if black
prod is
on negative,
off if it is on
positive.
65-110 AC
On
On
90-110 DC
On
On if black
prod is
on negative,
off if it is on
positive.
110-600 AC
On
On
110-600 DC
On
On if black
prod is
on negative,
off if it is on
positive.
Tester Operation Table
Indicator
Right LED
Right LED
Indicator
Off
No movement.
Off
No movement.
On
No movement.
On if red
No movement.
prod is
on negative,
off if prod is
reversed.
On
Little or no
movement.
On if red
Little or no
prod is
movement.
on negative
off if prod is
reversed.
On
Scale indicates
relative
magnitude.
On if red
Scale indicates
prod is
relative voltage.
on negative,
off if prod is
reversed.
tinuity check. If conti-
nuity LED turns "On,"
the fuse is good. If the
continuity LED does
not turn "On," the fuse
is defective. (61-086
only)
With power on: Place
tester across the "source" side of one
fuse and the load side of an adjoining
fuse. If no voltage is indicated, the fuse
next to the load side prod is blown. If
voltage is indicated, the fuse next to the
load side prod is OK. Repeat the same
test with the prods on the opposite side
of the same two fuses to check the other
fuse.
On a three phase circuit, repeat the
same test as above. An indication of no
voltage or lower than normal line volt-
age indicates the blown fuse.
• Finding Grounded Side of Line
(neutral)
Hold one test prod to the ground and
touch the other test prod to each of the
line terminals until one is found that
does not give a voltage indication. The
continuity LED should be "On." This is
the grounded side of the line.
• Testing for "Grounded" Side of
Motor or Appliance
With power to motor or appliance "Off,"